🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 600 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 6.44V (2.68%)
Voltage at Load End233.3 VLoss: 6.69 V (2028.0 W)
Power & Breaker (125%)72.75 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A570.32 V (237.63%)0.0 V940.75 V (391.98%)172867.8 WDrop/Amp High
12 AWG3.31 mm²20 A358.39 V (149.33%)0.0 V591.17 V (246.32%)108629.9 WDrop/Amp High
10 AWG5.26 mm²30 A225.52 V (93.97%)14.5 V372.01 V (155.0%)68358.4 WDrop/Amp High
8 AWG8.37 mm²50 A141.73 V (59.05%)98.3 V233.78 V (97.41%)42958.8 WDrop/Amp High
6 AWG13.3 mm²65 A89.19 V (37.16%)150.8 V147.13 V (61.3%)27035.0 WDrop/Amp High
4 AWG21.15 mm²85 A56.09 V (23.37%)183.9 V92.52 V (38.55%)17000.7 WDrop/Amp High
3 AWG26.67 mm²100 A44.48 V (18.53%)195.5 V73.37 V (30.57%)13482.0 WDrop/Amp High
2 AWG33.62 mm²115 A35.28 V (14.7%)204.7 V58.2 V (24.25%)10695.0 WDrop/Amp High
1 AWG42.41 mm²130 A27.97 V (11.65%)212.0 V46.14 V (19.22%)8478.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A22.18 V (9.24%)217.8 V36.58 V (15.24%)6722.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A17.59 V (7.33%)222.4 V29.02 V (12.09%)5332.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A13.95 V (5.81%)226.0 V23.02 V (9.59%)4229.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A11.07 V (4.61%)228.9 V18.25 V (7.61%)3354.2 W~ ≤5%
250 kcmil126.7 mm²255 A9.36 V (3.9%)230.6 V15.44 V (6.44%)2837.9 W~ ≤5%
300 kcmil152.0 mm²285 A7.8 V (3.25%)232.2 V12.87 V (5.36%)2365.6 W~ ≤5%
350 kcmil177.3 mm²310 A6.69 V (2.79%)233.3 V11.04 V (4.6%)2028.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A5.85 V (2.44%)234.1 V9.65 V (4.02%)1773.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A4.68 V (1.95%)235.3 V7.72 V (3.22%)1419.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.9 V (1.63%)236.1 V6.44 V (2.68%)1182.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.12 V (1.3%)236.9 V5.15 V (2.15%)946.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.34 V (0.98%)237.7 V3.86 V (1.61%)709.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 600 feet one-way at 240V (3-Phase), you need 350 kcmil copper wire. This produces a voltage drop of 6.69V (2.79%) and delivers 233.3V at the load.

What size aluminum wire is required for 175 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 6.44V (2.68%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.