🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 225 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 2.72%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 3.58V (2.99%)
Voltage at Load End116.7 VLoss: 3.26 V (733.1 W)
Power & Breaker (125%)27.0 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 225 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A317.51 V (264.59%)0.0 V523.75 V (436.46%)71440.2 WDrop/Amp High
12 AWG3.31 mm²20 A199.52 V (166.27%)0.0 V329.12 V (274.27%)44893.0 WDrop/Amp High
10 AWG5.26 mm²30 A125.56 V (104.63%)0.0 V207.11 V (172.59%)28250.1 WDrop/Amp High
8 AWG8.37 mm²50 A78.9 V (65.75%)41.1 V130.15 V (108.46%)17753.4 WDrop/Amp High
6 AWG13.3 mm²65 A49.66 V (41.38%)70.3 V81.91 V (68.26%)11172.6 WDrop/Amp High
4 AWG21.15 mm²85 A31.23 V (26.02%)88.8 V51.51 V (42.92%)7025.8 WDrop/Amp High
3 AWG26.67 mm²100 A24.76 V (20.64%)95.2 V40.85 V (34.04%)5571.6 WDrop/Amp High
2 AWG33.62 mm²115 A19.64 V (16.37%)100.4 V32.4 V (27.0%)4419.9 WDrop/Amp High
1 AWG42.41 mm²130 A15.57 V (12.98%)104.4 V25.69 V (21.41%)3503.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A12.35 V (10.29%)107.7 V20.37 V (16.97%)2778.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.79 V (8.16%)110.2 V16.16 V (13.46%)2203.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.77 V (6.47%)112.2 V12.81 V (10.68%)1748.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.16 V (5.13%)113.8 V10.16 V (8.47%)1386.2 WDrop/Amp High
250 kcmil126.7 mm²255 A5.21 V (4.34%)114.8 V8.6 V (7.17%)1172.8 W~ ≤5%
300 kcmil152.0 mm²285 A4.34 V (3.62%)115.7 V7.17 V (5.97%)977.6 W~ ≤5%
350 kcmil177.3 mm²310 A3.72 V (3.1%)116.3 V6.14 V (5.12%)838.1 W~ ≤5%
400 kcmil202.7 mm²335 A3.26 V (2.72%)116.7 V5.37 V (4.48%)733.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.61 V (2.17%)117.4 V4.3 V (3.58%)586.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.17 V (1.81%)117.8 V3.58 V (2.99%)488.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.74 V (1.45%)118.3 V2.87 V (2.39%)391.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.3 V (1.09%)118.7 V2.15 V (1.79%)293.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 225 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 225 feet one-way at 120V (1-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 3.26V (2.72%) and delivers 116.7V at the load.

What size aluminum wire is required for 225 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 3.58V (2.99%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.