🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 75 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 0.86%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 2.07V (0.99%)
Voltage at Load End206.2 VLoss: 1.78 V (693.1 W)
Power & Breaker (125%)81.06 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 75 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A91.66 V (44.07%)116.3 V151.19 V (72.69%)35720.1 WDrop/Amp High
12 AWG3.31 mm²20 A57.6 V (27.69%)150.4 V95.01 V (45.68%)22446.5 WDrop/Amp High
10 AWG5.26 mm²30 A36.24 V (17.43%)171.8 V59.79 V (28.74%)14125.1 WDrop/Amp High
8 AWG8.37 mm²50 A22.78 V (10.95%)185.2 V37.57 V (18.06%)8876.7 WDrop/Amp High
6 AWG13.3 mm²65 A14.33 V (6.89%)193.7 V23.65 V (11.37%)5586.3 WDrop/Amp High
4 AWG21.15 mm²85 A9.01 V (4.33%)199.0 V14.87 V (7.15%)3512.9 WDrop/Amp High
3 AWG26.67 mm²100 A7.15 V (3.44%)200.9 V11.79 V (5.67%)2785.8 WDrop/Amp High
2 AWG33.62 mm²115 A5.67 V (2.73%)202.3 V9.35 V (4.5%)2209.9 WDrop/Amp High
1 AWG42.41 mm²130 A4.5 V (2.16%)203.5 V7.42 V (3.57%)1751.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.56 V (1.71%)204.4 V5.88 V (2.83%)1389.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.83 V (1.36%)205.2 V4.66 V (2.24%)1101.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.24 V (1.08%)205.8 V3.7 V (1.78%)874.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.78 V (0.86%)206.2 V2.93 V (1.41%)693.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.5 V (0.72%)206.5 V2.48 V (1.19%)586.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.25 V (0.6%)206.7 V2.07 V (0.99%)488.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.08 V (0.52%)206.9 V1.77 V (0.85%)419.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.94 V (0.45%)207.1 V1.55 V (0.75%)366.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.75 V (0.36%)207.2 V1.24 V (0.6%)293.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.63 V (0.3%)207.4 V1.03 V (0.5%)244.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.5 V (0.24%)207.5 V0.83 V (0.4%)195.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.38 V (0.18%)207.6 V0.62 V (0.3%)146.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 75 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 75 feet one-way at 208V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 1.78V (0.86%) and delivers 206.2V at the load.

What size aluminum wire is required for 225 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 2.07V (0.99%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.