⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 30 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 0.34%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 0.83V (0.4%)
Voltage at Load End207.3 VLoss: 0.71 V (277.2 W)
Power & Breaker (125%)81.06 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 30 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A36.66 V (17.63%)171.3 V60.48 V (29.08%)14288.0 WDrop/Amp High
12 AWG3.31 mm²20 A23.04 V (11.08%)185.0 V38.0 V (18.27%)8978.6 WDrop/Amp High
10 AWG5.26 mm²30 A14.5 V (6.97%)193.5 V23.91 V (11.5%)5650.0 WDrop/Amp High
8 AWG8.37 mm²50 A9.11 V (4.38%)198.9 V15.03 V (7.23%)3550.7 WDrop/Amp High
6 AWG13.3 mm²65 A5.73 V (2.76%)202.3 V9.46 V (4.55%)2234.5 WDrop/Amp High
4 AWG21.15 mm²85 A3.61 V (1.73%)204.4 V5.95 V (2.86%)1405.2 WDrop/Amp High
3 AWG26.67 mm²100 A2.86 V (1.37%)205.1 V4.72 V (2.27%)1114.3 WDrop/Amp High
2 AWG33.62 mm²115 A2.27 V (1.09%)205.7 V3.74 V (1.8%)884.0 WDrop/Amp High
1 AWG42.41 mm²130 A1.8 V (0.86%)206.2 V2.97 V (1.43%)700.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.43 V (0.69%)206.6 V2.35 V (1.13%)555.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.13 V (0.54%)206.9 V1.87 V (0.9%)440.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A0.9 V (0.43%)207.1 V1.48 V (0.71%)349.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.71 V (0.34%)207.3 V1.17 V (0.56%)277.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.6 V (0.29%)207.4 V0.99 V (0.48%)234.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.5 V (0.24%)207.5 V0.83 V (0.4%)195.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.43 V (0.21%)207.6 V0.71 V (0.34%)167.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.38 V (0.18%)207.6 V0.62 V (0.3%)146.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.3 V (0.14%)207.7 V0.5 V (0.24%)117.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.25 V (0.12%)207.7 V0.41 V (0.2%)97.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.2 V (0.1%)207.8 V0.33 V (0.16%)78.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.15 V (0.07%)207.8 V0.25 V (0.12%)58.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 30 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 30 feet one-way at 208V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 0.71V (0.34%) and delivers 207.3V at the load.

What size aluminum wire is required for 225 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 0.83V (0.4%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.