⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 60 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 0.68%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 1.66V (0.8%)
Voltage at Load End206.6 VLoss: 1.42 V (554.5 W)
Power & Breaker (125%)81.06 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 60 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A73.33 V (35.25%)134.7 V120.95 V (58.15%)28576.1 WDrop/Amp High
12 AWG3.31 mm²20 A46.08 V (22.15%)161.9 V76.01 V (36.54%)17957.2 WDrop/Amp High
10 AWG5.26 mm²30 A29.0 V (13.94%)179.0 V47.83 V (23.0%)11300.1 WDrop/Amp High
8 AWG8.37 mm²50 A18.22 V (8.76%)189.8 V30.06 V (14.45%)7101.3 WDrop/Amp High
6 AWG13.3 mm²65 A11.47 V (5.51%)196.5 V18.92 V (9.09%)4469.0 WDrop/Amp High
4 AWG21.15 mm²85 A7.21 V (3.47%)200.8 V11.9 V (5.72%)2810.3 WDrop/Amp High
3 AWG26.67 mm²100 A5.72 V (2.75%)202.3 V9.43 V (4.54%)2228.7 WDrop/Amp High
2 AWG33.62 mm²115 A4.54 V (2.18%)203.5 V7.48 V (3.6%)1767.9 WDrop/Amp High
1 AWG42.41 mm²130 A3.6 V (1.73%)204.4 V5.93 V (2.85%)1401.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.85 V (1.37%)205.1 V4.7 V (2.26%)1111.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.26 V (1.09%)205.7 V3.73 V (1.79%)881.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.79 V (0.86%)206.2 V2.96 V (1.42%)699.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.42 V (0.68%)206.6 V2.35 V (1.13%)554.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.2 V (0.58%)206.8 V1.99 V (0.95%)469.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.0 V (0.48%)207.0 V1.66 V (0.8%)391.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.86 V (0.41%)207.1 V1.42 V (0.68%)335.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.75 V (0.36%)207.2 V1.24 V (0.6%)293.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.6 V (0.29%)207.4 V0.99 V (0.48%)234.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.5 V (0.24%)207.5 V0.83 V (0.4%)195.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.4 V (0.19%)207.6 V0.66 V (0.32%)156.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.3 V (0.14%)207.7 V0.5 V (0.24%)117.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 60 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 60 feet one-way at 208V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 1.42V (0.68%) and delivers 206.6V at the load.

What size aluminum wire is required for 225 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 1.66V (0.8%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.