🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 175 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 2.0%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 4.83V (2.32%)
Voltage at Load End203.9 VLoss: 4.15 V (1617.2 W)
Power & Breaker (125%)81.06 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 175 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A213.87 V (102.82%)0.0 V352.78 V (169.61%)83347.0 WDrop/Amp High
12 AWG3.31 mm²20 A134.39 V (64.61%)73.6 V221.69 V (106.58%)52375.1 WDrop/Amp High
10 AWG5.26 mm²30 A84.57 V (40.66%)123.4 V139.5 V (67.07%)32958.5 WDrop/Amp High
8 AWG8.37 mm²50 A53.15 V (25.55%)154.9 V87.67 V (42.15%)20712.3 WDrop/Amp High
6 AWG13.3 mm²65 A33.45 V (16.08%)174.6 V55.17 V (26.53%)13034.7 WDrop/Amp High
4 AWG21.15 mm²85 A21.03 V (10.11%)187.0 V34.69 V (16.68%)8196.8 WDrop/Amp High
3 AWG26.67 mm²100 A16.68 V (8.02%)191.3 V27.51 V (13.23%)6500.2 WDrop/Amp High
2 AWG33.62 mm²115 A13.23 V (6.36%)194.8 V21.83 V (10.49%)5156.5 WDrop/Amp High
1 AWG42.41 mm²130 A10.49 V (5.04%)197.5 V17.3 V (8.32%)4087.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.32 V (4.0%)199.7 V13.72 V (6.6%)3241.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.6 V (3.17%)201.4 V10.88 V (5.23%)2571.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.23 V (2.52%)202.8 V8.63 V (4.15%)2039.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.15 V (2.0%)203.9 V6.85 V (3.29%)1617.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.51 V (1.69%)204.5 V5.79 V (2.78%)1368.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.93 V (1.41%)205.1 V4.83 V (2.32%)1140.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.51 V (1.21%)205.5 V4.14 V (1.99%)977.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.19 V (1.06%)205.8 V3.62 V (1.74%)855.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.76 V (0.84%)206.2 V2.9 V (1.39%)684.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.46 V (0.7%)206.5 V2.41 V (1.16%)570.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.17 V (0.56%)206.8 V1.93 V (0.93%)456.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.88 V (0.42%)207.1 V1.45 V (0.7%)342.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 175 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 175 feet one-way at 208V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 4.15V (2.0%) and delivers 203.9V at the load.

What size aluminum wire is required for 225 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 4.83V (2.32%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.