⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 150 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 1.71%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 4.14V (1.99%)
Voltage at Load End204.4 VLoss: 3.56 V (1386.2 W)
Power & Breaker (125%)81.06 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 150 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A183.32 V (88.13%)24.7 V302.39 V (145.38%)71440.2 WDrop/Amp High
12 AWG3.31 mm²20 A115.2 V (55.38%)92.8 V190.02 V (91.36%)44893.0 WDrop/Amp High
10 AWG5.26 mm²30 A72.49 V (34.85%)135.5 V119.57 V (57.49%)28250.1 WDrop/Amp High
8 AWG8.37 mm²50 A45.56 V (21.9%)162.4 V75.14 V (36.13%)17753.4 WDrop/Amp High
6 AWG13.3 mm²65 A28.67 V (13.78%)179.3 V47.29 V (22.74%)11172.6 WDrop/Amp High
4 AWG21.15 mm²85 A18.03 V (8.67%)190.0 V29.74 V (14.3%)7025.8 WDrop/Amp High
3 AWG26.67 mm²100 A14.3 V (6.87%)193.7 V23.58 V (11.34%)5571.6 WDrop/Amp High
2 AWG33.62 mm²115 A11.34 V (5.45%)196.7 V18.71 V (8.99%)4419.9 WDrop/Amp High
1 AWG42.41 mm²130 A8.99 V (4.32%)199.0 V14.83 V (7.13%)3503.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.13 V (3.43%)200.9 V11.76 V (5.65%)2778.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.65 V (2.72%)202.3 V9.33 V (4.48%)2203.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.49 V (2.16%)203.5 V7.4 V (3.56%)1748.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.56 V (1.71%)204.4 V5.87 V (2.82%)1386.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.01 V (1.45%)205.0 V4.96 V (2.39%)1172.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.51 V (1.21%)205.5 V4.14 V (1.99%)977.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.15 V (1.03%)205.8 V3.55 V (1.71%)838.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.88 V (0.9%)206.1 V3.1 V (1.49%)733.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.5 V (0.72%)206.5 V2.48 V (1.19%)586.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.25 V (0.6%)206.7 V2.07 V (0.99%)488.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.0 V (0.48%)207.0 V1.66 V (0.8%)391.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.75 V (0.36%)207.2 V1.24 V (0.6%)293.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 150 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 150 feet one-way at 208V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 3.56V (1.71%) and delivers 204.4V at the load.

What size aluminum wire is required for 225 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 4.14V (1.99%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.