🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 125 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 1.43%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 3.45V (1.66%)
Voltage at Load End205.0 VLoss: 2.96 V (1155.1 W)
Power & Breaker (125%)81.06 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 125 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A152.76 V (73.44%)55.2 V251.99 V (121.15%)59533.5 WDrop/Amp High
12 AWG3.31 mm²20 A96.0 V (46.15%)112.0 V158.35 V (76.13%)37410.8 WDrop/Amp High
10 AWG5.26 mm²30 A60.41 V (29.04%)147.6 V99.65 V (47.91%)23541.8 WDrop/Amp High
8 AWG8.37 mm²50 A37.96 V (18.25%)170.0 V62.62 V (30.11%)14794.5 WDrop/Amp High
6 AWG13.3 mm²65 A23.89 V (11.49%)184.1 V39.41 V (18.95%)9310.5 WDrop/Amp High
4 AWG21.15 mm²85 A15.02 V (7.22%)193.0 V24.78 V (11.91%)5854.8 WDrop/Amp High
3 AWG26.67 mm²100 A11.91 V (5.73%)196.1 V19.65 V (9.45%)4643.0 WDrop/Amp High
2 AWG33.62 mm²115 A9.45 V (4.54%)198.5 V15.59 V (7.5%)3683.2 WDrop/Amp High
1 AWG42.41 mm²130 A7.49 V (3.6%)200.5 V12.36 V (5.94%)2919.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.94 V (2.86%)202.1 V9.8 V (4.71%)2315.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.71 V (2.27%)203.3 V7.77 V (3.74%)1836.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.74 V (1.8%)204.3 V6.17 V (2.96%)1456.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.96 V (1.43%)205.0 V4.89 V (2.35%)1155.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.51 V (1.21%)205.5 V4.14 V (1.99%)977.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.09 V (1.01%)205.9 V3.45 V (1.66%)814.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.79 V (0.86%)206.2 V2.96 V (1.42%)698.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.57 V (0.75%)206.4 V2.59 V (1.24%)610.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.25 V (0.6%)206.7 V2.07 V (0.99%)488.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.05 V (0.5%)207.0 V1.72 V (0.83%)407.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.84 V (0.4%)207.2 V1.38 V (0.66%)325.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.63 V (0.3%)207.4 V1.03 V (0.5%)244.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 125 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 125 feet one-way at 208V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 2.96V (1.43%) and delivers 205.0V at the load.

What size aluminum wire is required for 225 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 3.45V (1.66%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.