🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 120 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 1.37%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 3.31V (1.59%)
Voltage at Load End205.2 VLoss: 2.85 V (1108.9 W)
Power & Breaker (125%)81.06 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 120 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A146.65 V (70.51%)61.3 V241.91 V (116.3%)57152.2 WDrop/Amp High
12 AWG3.31 mm²20 A92.16 V (44.31%)115.8 V152.01 V (73.08%)35914.4 WDrop/Amp High
10 AWG5.26 mm²30 A57.99 V (27.88%)150.0 V95.66 V (45.99%)22600.1 WDrop/Amp High
8 AWG8.37 mm²50 A36.44 V (17.52%)171.6 V60.12 V (28.9%)14202.7 WDrop/Amp High
6 AWG13.3 mm²65 A22.94 V (11.03%)185.1 V37.83 V (18.19%)8938.1 WDrop/Amp High
4 AWG21.15 mm²85 A14.42 V (6.93%)193.6 V23.79 V (11.44%)5620.6 WDrop/Amp High
3 AWG26.67 mm²100 A11.44 V (5.5%)196.6 V18.87 V (9.07%)4457.3 WDrop/Amp High
2 AWG33.62 mm²115 A9.07 V (4.36%)198.9 V14.97 V (7.2%)3535.9 WDrop/Amp High
1 AWG42.41 mm²130 A7.19 V (3.46%)200.8 V11.86 V (5.7%)2803.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.7 V (2.74%)202.3 V9.41 V (4.52%)2222.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.52 V (2.17%)203.5 V7.46 V (3.59%)1763.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.59 V (1.73%)204.4 V5.92 V (2.85%)1398.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.85 V (1.37%)205.2 V4.69 V (2.26%)1108.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.41 V (1.16%)205.6 V3.97 V (1.91%)938.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.01 V (0.96%)206.0 V3.31 V (1.59%)782.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.72 V (0.83%)206.3 V2.84 V (1.36%)670.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.5 V (0.72%)206.5 V2.48 V (1.19%)586.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.2 V (0.58%)206.8 V1.99 V (0.95%)469.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.0 V (0.48%)207.0 V1.66 V (0.8%)391.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.8 V (0.39%)207.2 V1.32 V (0.64%)312.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.6 V (0.29%)207.4 V0.99 V (0.48%)234.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 120 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 120 feet one-way at 208V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 2.85V (1.37%) and delivers 205.2V at the load.

What size aluminum wire is required for 225 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 3.31V (1.59%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.