🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 275 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.93%
Aluminum Wire (≤3% Drop)6 AWGDrop: 9.63V (2.01%)
Voltage at Load End470.7 VLoss: 9.28 V (401.8 W)
Power & Breaker (125%)20.78 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 275 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A37.34 V (7.78%)442.7 V61.6 V (12.83%)1617.0 WDrop/Amp High
12 AWG3.31 mm²20 A23.47 V (4.89%)456.5 V38.71 V (8.06%)1016.1 WDrop/Amp High
10 AWG5.26 mm²30 A14.77 V (3.08%)465.2 V24.36 V (5.07%)639.4 W~ ≤5%
8 AWG8.37 mm²50 A9.28 V (1.93%)470.7 V15.31 V (3.19%)401.8 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A5.84 V (1.22%)474.2 V9.63 V (2.01%)252.9 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A3.67 V (0.77%)476.3 V6.06 V (1.26%)159.0 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.91 V (0.61%)477.1 V4.8 V (1.0%)126.1 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.31 V (0.48%)477.7 V3.81 V (0.79%)100.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.83 V (0.38%)478.2 V3.02 V (0.63%)79.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.45 V (0.3%)478.5 V2.4 V (0.5%)62.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.15 V (0.24%)478.8 V1.9 V (0.4%)49.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.91 V (0.19%)479.1 V1.51 V (0.31%)39.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.72 V (0.15%)479.3 V1.2 V (0.25%)31.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.61 V (0.13%)479.4 V1.01 V (0.21%)26.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.51 V (0.11%)479.5 V0.84 V (0.18%)22.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.44 V (0.09%)479.6 V0.72 V (0.15%)19.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.38 V (0.08%)479.6 V0.63 V (0.13%)16.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.31 V (0.06%)479.7 V0.51 V (0.11%)13.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.26 V (0.05%)479.7 V0.42 V (0.09%)11.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.2 V (0.04%)479.8 V0.34 V (0.07%)8.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.15 V (0.03%)479.8 V0.25 V (0.05%)6.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 275 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 275 feet one-way at 480V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 9.28V (1.93%) and delivers 470.7V at the load.

What size aluminum wire is required for 25 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 9.63V (2.01%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.