275 Amp Wire Size at 225 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.65%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 3.5V (2.92%)
Voltage at Load End116.8 VLoss: 3.19 V (876.0 W)
Power & Breaker (125%)33.0 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 225 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A388.07 V (323.39%)0.0 V640.13 V (533.45%)106719.4 WDrop/Amp High
12 AWG3.31 mm²20 A243.86 V (203.22%)0.0 V402.26 V (335.22%)67062.3 WDrop/Amp High
10 AWG5.26 mm²30 A153.46 V (127.88%)0.0 V253.13 V (210.94%)42200.8 WDrop/Amp High
8 AWG8.37 mm²50 A96.44 V (80.37%)23.6 V159.08 V (132.56%)26520.5 WDrop/Amp High
6 AWG13.3 mm²65 A60.69 V (50.58%)59.3 V100.11 V (83.43%)16689.9 WDrop/Amp High
4 AWG21.15 mm²85 A38.16 V (31.8%)81.8 V62.95 V (52.46%)10495.3 WDrop/Amp High
3 AWG26.67 mm²100 A30.27 V (25.22%)89.7 V49.92 V (41.6%)8323.1 WDrop/Amp High
2 AWG33.62 mm²115 A24.01 V (20.01%)96.0 V39.6 V (33.0%)6602.5 WDrop/Amp High
1 AWG42.41 mm²130 A19.03 V (15.86%)101.0 V31.4 V (26.16%)5234.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A15.09 V (12.58%)104.9 V24.89 V (20.74%)4149.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.97 V (9.98%)108.0 V19.75 V (16.46%)3292.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.5 V (7.91%)110.5 V15.66 V (13.05%)2611.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.53 V (6.27%)112.5 V12.42 V (10.35%)2070.7 WDrop/Amp High
250 kcmil126.7 mm²255 A6.37 V (5.31%)113.6 V10.51 V (8.76%)1752.0 WDrop/Amp High
300 kcmil152.0 mm²285 A5.31 V (4.43%)114.7 V8.76 V (7.3%)1460.4 W~ ≤5%
350 kcmil177.3 mm²310 A4.55 V (3.79%)115.4 V7.51 V (6.26%)1252.0 W~ ≤5%
400 kcmil202.7 mm²335 A3.98 V (3.32%)116.0 V6.57 V (5.47%)1095.1 W~ ≤5%
500 kcmil253.4 mm²380 A3.19 V (2.65%)116.8 V5.25 V (4.38%)876.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.66 V (2.21%)117.3 V4.38 V (3.65%)730.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.12 V (1.77%)117.9 V3.5 V (2.92%)584.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.59 V (1.33%)118.4 V2.63 V (2.19%)438.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 225 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 225 feet one-way at 120V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 3.19V (2.65%) and delivers 116.8V at the load.

What size aluminum wire is required for 275 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 3.5V (2.92%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.