🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 275 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 2.7%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 5.56V (2.67%)
Voltage at Load End202.4 VLoss: 5.62 V (2677.3 W)
Power & Breaker (125%)99.07 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 275 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A410.76 V (197.48%)0.0 V677.57 V (325.75%)195652.2 WDrop/Amp High
12 AWG3.31 mm²20 A258.12 V (124.1%)0.0 V425.78 V (204.7%)122947.6 WDrop/Amp High
10 AWG5.26 mm²30 A162.43 V (78.09%)45.6 V267.94 V (128.82%)77368.2 WDrop/Amp High
8 AWG8.37 mm²50 A102.08 V (49.08%)105.9 V168.38 V (80.95%)48620.9 WDrop/Amp High
6 AWG13.3 mm²65 A64.24 V (30.88%)143.8 V105.97 V (50.94%)30598.2 WDrop/Amp High
4 AWG21.15 mm²85 A40.4 V (19.42%)167.6 V66.64 V (32.04%)19241.4 WDrop/Amp High
3 AWG26.67 mm²100 A32.04 V (15.4%)176.0 V52.84 V (25.41%)15259.0 WDrop/Amp High
2 AWG33.62 mm²115 A25.41 V (12.22%)182.6 V41.92 V (20.15%)12104.6 WDrop/Amp High
1 AWG42.41 mm²130 A20.15 V (9.69%)187.9 V33.23 V (15.98%)9595.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A15.97 V (7.68%)192.0 V26.35 V (12.67%)7608.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.67 V (6.09%)195.3 V20.9 V (10.05%)6035.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.05 V (4.83%)197.9 V16.58 V (7.97%)4787.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.97 V (3.83%)200.0 V13.15 V (6.32%)3796.2 WDrop/Amp High
250 kcmil126.7 mm²255 A6.74 V (3.24%)201.3 V11.12 V (5.35%)3212.0 WDrop/Amp High
300 kcmil152.0 mm²285 A5.62 V (2.7%)202.4 V9.27 V (4.46%)2677.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A4.82 V (2.32%)203.2 V7.95 V (3.82%)2295.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A4.22 V (2.03%)203.8 V6.95 V (3.34%)2007.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.37 V (1.62%)204.6 V5.56 V (2.67%)1606.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.81 V (1.35%)205.2 V4.64 V (2.23%)1338.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.25 V (1.08%)205.8 V3.71 V (1.78%)1070.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.69 V (0.81%)206.3 V2.78 V (1.34%)803.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 275 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 275 feet one-way at 208V (3-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 5.62V (2.7%) and delivers 202.4V at the load.

What size aluminum wire is required for 275 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 5.56V (2.67%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.