🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 750 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 2.74%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 12.64V (2.63%)
Voltage at Load End466.9 VLoss: 13.14 V (6259.9 W)
Power & Breaker (125%)228.63 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 750 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1120.26 V (233.39%)0.0 V1847.91 V (384.98%)533596.9 WDrop/Amp High
12 AWG3.31 mm²20 A703.97 V (146.66%)0.0 V1161.22 V (241.92%)335311.7 WDrop/Amp High
10 AWG5.26 mm²30 A442.99 V (92.29%)37.0 V730.73 V (152.24%)211004.1 WDrop/Amp High
8 AWG8.37 mm²50 A278.39 V (58.0%)201.6 V459.22 V (95.67%)132602.3 WDrop/Amp High
6 AWG13.3 mm²65 A175.2 V (36.5%)304.8 V289.0 V (60.21%)83449.7 WDrop/Amp High
4 AWG21.15 mm²85 A110.17 V (22.95%)369.8 V181.73 V (37.86%)52476.7 WDrop/Amp High
3 AWG26.67 mm²100 A87.37 V (18.2%)392.6 V144.12 V (30.02%)41615.4 WDrop/Amp High
2 AWG33.62 mm²115 A69.31 V (14.44%)410.7 V114.33 V (23.82%)33012.5 WDrop/Amp High
1 AWG42.41 mm²130 A54.94 V (11.45%)425.1 V90.63 V (18.88%)26170.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A43.56 V (9.08%)436.4 V71.86 V (14.97%)20749.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A34.56 V (7.2%)445.4 V57.0 V (11.88%)16459.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A27.41 V (5.71%)452.6 V45.21 V (9.42%)13055.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A21.74 V (4.53%)458.3 V35.85 V (7.47%)10353.4 WDrop/Amp High
250 kcmil126.7 mm²255 A18.39 V (3.83%)461.6 V30.34 V (6.32%)8759.9 WDrop/Amp High
300 kcmil152.0 mm²285 A15.33 V (3.19%)464.7 V25.29 V (5.27%)7301.9 W~ ≤5%
350 kcmil177.3 mm²310 A13.14 V (2.74%)466.9 V21.68 V (4.52%)6259.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A11.5 V (2.39%)468.5 V18.96 V (3.95%)5475.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A9.2 V (1.92%)470.8 V15.17 V (3.16%)4380.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A7.66 V (1.6%)472.3 V12.64 V (2.63%)3650.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A6.13 V (1.28%)473.9 V10.11 V (2.11%)2920.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A4.6 V (0.96%)475.4 V7.59 V (1.58%)2190.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 750 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 750 feet one-way at 480V (3-Phase), you need 350 kcmil copper wire. This produces a voltage drop of 13.14V (2.74%) and delivers 466.9V at the load.

What size aluminum wire is required for 275 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 12.64V (2.63%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.