🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 100 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 0.87%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 2.3V (0.96%)
Voltage at Load End237.9 VLoss: 2.09 V (679.8 W)
Power & Breaker (125%)78.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 100 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A203.83 V (84.93%)36.2 V336.23 V (140.1%)66246.4 WDrop/Amp High
12 AWG3.31 mm²20 A128.09 V (53.37%)111.9 V211.29 V (88.04%)41629.1 WDrop/Amp High
10 AWG5.26 mm²30 A80.6 V (33.58%)159.4 V132.96 V (55.4%)26196.3 WDrop/Amp High
8 AWG8.37 mm²50 A50.65 V (21.11%)189.3 V83.56 V (34.81%)16462.7 WDrop/Amp High
6 AWG13.3 mm²65 A31.88 V (13.28%)208.1 V52.58 V (21.91%)10360.3 WDrop/Amp High
4 AWG21.15 mm²85 A20.05 V (8.35%)220.0 V33.07 V (13.78%)6515.0 WDrop/Amp High
3 AWG26.67 mm²100 A15.9 V (6.62%)224.1 V26.22 V (10.93%)5166.6 WDrop/Amp High
2 AWG33.62 mm²115 A12.61 V (5.25%)227.4 V20.8 V (8.67%)4098.5 WDrop/Amp High
1 AWG42.41 mm²130 A10.0 V (4.17%)230.0 V16.49 V (6.87%)3249.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.93 V (3.3%)232.1 V13.07 V (5.45%)2576.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.29 V (2.62%)233.7 V10.37 V (4.32%)2043.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.99 V (2.08%)235.0 V8.23 V (3.43%)1620.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.96 V (1.65%)236.0 V6.52 V (2.72%)1285.4 WDrop/Amp High
250 kcmil126.7 mm²255 A3.35 V (1.39%)236.7 V5.52 V (2.3%)1087.5 WDrop/Amp High
300 kcmil152.0 mm²285 A2.79 V (1.16%)237.2 V4.6 V (1.92%)906.5 WDrop/Amp High
350 kcmil177.3 mm²310 A2.39 V (1.0%)237.6 V3.94 V (1.64%)777.2 WDrop/Amp High
400 kcmil202.7 mm²335 A2.09 V (0.87%)237.9 V3.45 V (1.44%)679.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.67 V (0.7%)238.3 V2.76 V (1.15%)543.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.39 V (0.58%)238.6 V2.3 V (0.96%)453.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.12 V (0.46%)238.9 V1.84 V (0.77%)362.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.84 V (0.35%)239.2 V1.38 V (0.58%)271.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 100 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 100 feet one-way at 240V (1-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 2.09V (0.87%) and delivers 237.9V at the load.

What size aluminum wire is required for 325 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 2.3V (0.96%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.