⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 150 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 1.31%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 3.45V (1.44%)
Voltage at Load End236.9 VLoss: 3.14 V (1019.7 W)
Power & Breaker (125%)78.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 150 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A305.75 V (127.4%)0.0 V504.35 V (210.15%)99369.6 WDrop/Amp High
12 AWG3.31 mm²20 A192.13 V (80.06%)47.9 V316.93 V (132.06%)62443.7 WDrop/Amp High
10 AWG5.26 mm²30 A120.91 V (50.38%)119.1 V199.44 V (83.1%)39294.4 WDrop/Amp High
8 AWG8.37 mm²50 A75.98 V (31.66%)164.0 V125.33 V (52.22%)24694.0 WDrop/Amp High
6 AWG13.3 mm²65 A47.82 V (19.92%)192.2 V78.88 V (32.86%)15540.5 WDrop/Amp High
4 AWG21.15 mm²85 A30.07 V (12.53%)209.9 V49.6 V (20.67%)9772.5 WDrop/Amp High
3 AWG26.67 mm²100 A23.85 V (9.94%)216.2 V39.33 V (16.39%)7749.9 WDrop/Amp High
2 AWG33.62 mm²115 A18.92 V (7.88%)221.1 V31.2 V (13.0%)6147.8 WDrop/Amp High
1 AWG42.41 mm²130 A15.0 V (6.25%)225.0 V24.74 V (10.31%)4873.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.89 V (4.95%)228.1 V19.61 V (8.17%)3864.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.43 V (3.93%)230.6 V15.56 V (6.48%)3065.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.48 V (3.12%)232.5 V12.34 V (5.14%)2431.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.93 V (2.47%)234.1 V9.79 V (4.08%)1928.1 WDrop/Amp High
250 kcmil126.7 mm²255 A5.02 V (2.09%)235.0 V8.28 V (3.45%)1631.3 WDrop/Amp High
300 kcmil152.0 mm²285 A4.18 V (1.74%)235.8 V6.9 V (2.88%)1359.8 WDrop/Amp High
350 kcmil177.3 mm²310 A3.59 V (1.49%)236.4 V5.92 V (2.47%)1165.8 WDrop/Amp High
400 kcmil202.7 mm²335 A3.14 V (1.31%)236.9 V5.18 V (2.16%)1019.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.51 V (1.05%)237.5 V4.14 V (1.72%)815.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.09 V (0.87%)237.9 V3.45 V (1.44%)679.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.67 V (0.7%)238.3 V2.76 V (1.15%)543.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.26 V (0.52%)238.7 V2.07 V (0.86%)407.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 150 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 150 feet one-way at 240V (1-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 3.14V (1.31%) and delivers 236.9V at the load.

What size aluminum wire is required for 325 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 3.45V (1.44%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.