🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 80 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 0.7%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 1.84V (0.77%)
Voltage at Load End238.3 VLoss: 1.67 V (543.8 W)
Power & Breaker (125%)78.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 80 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A163.07 V (67.94%)76.9 V268.99 V (112.08%)52997.1 WDrop/Amp High
12 AWG3.31 mm²20 A102.47 V (42.7%)137.5 V169.03 V (70.43%)33303.3 WDrop/Amp High
10 AWG5.26 mm²30 A64.48 V (26.87%)175.5 V106.37 V (44.32%)20957.0 WDrop/Amp High
8 AWG8.37 mm²50 A40.52 V (16.88%)199.5 V66.84 V (27.85%)13170.1 WDrop/Amp High
6 AWG13.3 mm²65 A25.5 V (10.63%)214.5 V42.07 V (17.53%)8288.3 WDrop/Amp High
4 AWG21.15 mm²85 A16.04 V (6.68%)224.0 V26.45 V (11.02%)5212.0 WDrop/Amp High
3 AWG26.67 mm²100 A12.72 V (5.3%)227.3 V20.98 V (8.74%)4133.3 WDrop/Amp High
2 AWG33.62 mm²115 A10.09 V (4.2%)229.9 V16.64 V (6.93%)3278.8 WDrop/Amp High
1 AWG42.41 mm²130 A8.0 V (3.33%)232.0 V13.19 V (5.5%)2599.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.34 V (2.64%)233.7 V10.46 V (4.36%)2060.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.03 V (2.1%)235.0 V8.3 V (3.46%)1634.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.99 V (1.66%)236.0 V6.58 V (2.74%)1296.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.16 V (1.32%)236.8 V5.22 V (2.17%)1028.3 WDrop/Amp High
250 kcmil126.7 mm²255 A2.68 V (1.12%)237.3 V4.42 V (1.84%)870.0 WDrop/Amp High
300 kcmil152.0 mm²285 A2.23 V (0.93%)237.8 V3.68 V (1.53%)725.2 WDrop/Amp High
350 kcmil177.3 mm²310 A1.91 V (0.8%)238.1 V3.16 V (1.31%)621.7 WDrop/Amp High
400 kcmil202.7 mm²335 A1.67 V (0.7%)238.3 V2.76 V (1.15%)543.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.34 V (0.56%)238.7 V2.21 V (0.92%)435.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.12 V (0.46%)238.9 V1.84 V (0.77%)362.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.89 V (0.37%)239.1 V1.47 V (0.61%)290.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.67 V (0.28%)239.3 V1.1 V (0.46%)217.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 80 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 80 feet one-way at 240V (1-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 1.67V (0.7%) and delivers 238.3V at the load.

What size aluminum wire is required for 325 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 1.84V (0.77%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.