325 Amp Wire Size at 175 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 1.53%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 4.03V (1.68%)
Voltage at Load End236.3 VLoss: 3.66 V (1189.6 W)
Power & Breaker (125%)78.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A356.71 V (148.63%)0.0 V588.41 V (245.17%)115931.2 WDrop/Amp High
12 AWG3.31 mm²20 A224.16 V (93.4%)15.8 V369.75 V (154.06%)72851.0 WDrop/Amp High
10 AWG5.26 mm²30 A141.06 V (58.77%)98.9 V232.68 V (96.95%)45843.5 WDrop/Amp High
8 AWG8.37 mm²50 A88.65 V (36.94%)151.4 V146.22 V (60.93%)28809.7 WDrop/Amp High
6 AWG13.3 mm²65 A55.79 V (23.24%)184.2 V92.02 V (38.34%)18130.6 WDrop/Amp High
4 AWG21.15 mm²85 A35.08 V (14.62%)204.9 V57.87 V (24.11%)11401.3 WDrop/Amp High
3 AWG26.67 mm²100 A27.82 V (11.59%)212.2 V45.89 V (19.12%)9041.5 WDrop/Amp High
2 AWG33.62 mm²115 A22.07 V (9.2%)217.9 V36.4 V (15.17%)7172.4 WDrop/Amp High
1 AWG42.41 mm²130 A17.49 V (7.29%)222.5 V28.86 V (12.02%)5685.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.87 V (5.78%)226.1 V22.88 V (9.53%)4508.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.0 V (4.58%)229.0 V18.15 V (7.56%)3576.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.73 V (3.64%)231.3 V14.4 V (6.0%)2836.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.92 V (2.88%)233.1 V11.42 V (4.76%)2249.4 WDrop/Amp High
250 kcmil126.7 mm²255 A5.86 V (2.44%)234.1 V9.66 V (4.02%)1903.2 WDrop/Amp High
300 kcmil152.0 mm²285 A4.88 V (2.03%)235.1 V8.05 V (3.35%)1586.4 WDrop/Amp High
350 kcmil177.3 mm²310 A4.18 V (1.74%)235.8 V6.9 V (2.88%)1360.0 WDrop/Amp High
400 kcmil202.7 mm²335 A3.66 V (1.53%)236.3 V6.04 V (2.52%)1189.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.93 V (1.22%)237.1 V4.83 V (2.01%)951.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.44 V (1.02%)237.6 V4.03 V (1.68%)793.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.95 V (0.81%)238.0 V3.22 V (1.34%)634.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.46 V (0.61%)238.5 V2.42 V (1.01%)475.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 175 feet one-way at 240V (1-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 3.66V (1.53%) and delivers 236.3V at the load.

What size aluminum wire is required for 325 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 4.03V (1.68%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.