⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 60 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 0.52%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 1.38V (0.58%)
Voltage at Load End238.7 VLoss: 1.25 V (407.9 W)
Power & Breaker (125%)78.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 60 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A122.3 V (50.96%)117.7 V201.74 V (84.06%)39747.8 WDrop/Amp High
12 AWG3.31 mm²20 A76.85 V (32.02%)163.1 V126.77 V (52.82%)24977.5 WDrop/Amp High
10 AWG5.26 mm²30 A48.36 V (20.15%)191.6 V79.78 V (33.24%)15717.8 WDrop/Amp High
8 AWG8.37 mm²50 A30.39 V (12.66%)209.6 V50.13 V (20.89%)9877.6 WDrop/Amp High
6 AWG13.3 mm²65 A19.13 V (7.97%)220.9 V31.55 V (13.15%)6216.2 WDrop/Amp High
4 AWG21.15 mm²85 A12.03 V (5.01%)228.0 V19.84 V (8.27%)3909.0 WDrop/Amp High
3 AWG26.67 mm²100 A9.54 V (3.97%)230.5 V15.73 V (6.56%)3099.9 WDrop/Amp High
2 AWG33.62 mm²115 A7.57 V (3.15%)232.4 V12.48 V (5.2%)2459.1 WDrop/Amp High
1 AWG42.41 mm²130 A6.0 V (2.5%)234.0 V9.89 V (4.12%)1949.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.76 V (1.98%)235.2 V7.84 V (3.27%)1545.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.77 V (1.57%)236.2 V6.22 V (2.59%)1226.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.99 V (1.25%)237.0 V4.94 V (2.06%)972.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.37 V (0.99%)237.6 V3.91 V (1.63%)771.2 WDrop/Amp High
250 kcmil126.7 mm²255 A2.01 V (0.84%)238.0 V3.31 V (1.38%)652.5 WDrop/Amp High
300 kcmil152.0 mm²285 A1.67 V (0.7%)238.3 V2.76 V (1.15%)543.9 WDrop/Amp High
350 kcmil177.3 mm²310 A1.43 V (0.6%)238.6 V2.37 V (0.99%)466.3 WDrop/Amp High
400 kcmil202.7 mm²335 A1.25 V (0.52%)238.7 V2.07 V (0.86%)407.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.0 V (0.42%)239.0 V1.66 V (0.69%)326.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.84 V (0.35%)239.2 V1.38 V (0.58%)272.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.67 V (0.28%)239.3 V1.1 V (0.46%)217.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.5 V (0.21%)239.5 V0.83 V (0.35%)163.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 60 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 60 feet one-way at 240V (1-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 1.25V (0.52%) and delivers 238.7V at the load.

What size aluminum wire is required for 325 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 1.38V (0.58%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.