⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 20 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 0.17%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 0.46V (0.19%)
Voltage at Load End239.6 VLoss: 0.42 V (136.0 W)
Power & Breaker (125%)78.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 20 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A40.77 V (16.99%)199.2 V67.25 V (28.02%)13249.3 WDrop/Amp High
12 AWG3.31 mm²20 A25.62 V (10.67%)214.4 V42.26 V (17.61%)8325.8 WDrop/Amp High
10 AWG5.26 mm²30 A16.12 V (6.72%)223.9 V26.59 V (11.08%)5239.3 WDrop/Amp High
8 AWG8.37 mm²50 A10.13 V (4.22%)229.9 V16.71 V (6.96%)3292.5 WDrop/Amp High
6 AWG13.3 mm²65 A6.38 V (2.66%)233.6 V10.52 V (4.38%)2072.1 WDrop/Amp High
4 AWG21.15 mm²85 A4.01 V (1.67%)236.0 V6.61 V (2.76%)1303.0 WDrop/Amp High
3 AWG26.67 mm²100 A3.18 V (1.32%)236.8 V5.24 V (2.19%)1033.3 WDrop/Amp High
2 AWG33.62 mm²115 A2.52 V (1.05%)237.5 V4.16 V (1.73%)819.7 WDrop/Amp High
1 AWG42.41 mm²130 A2.0 V (0.83%)238.0 V3.3 V (1.37%)649.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.59 V (0.66%)238.4 V2.61 V (1.09%)515.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.26 V (0.52%)238.7 V2.07 V (0.86%)408.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.0 V (0.42%)239.0 V1.65 V (0.69%)324.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.79 V (0.33%)239.2 V1.3 V (0.54%)257.1 WDrop/Amp High
250 kcmil126.7 mm²255 A0.67 V (0.28%)239.3 V1.1 V (0.46%)217.5 WDrop/Amp High
300 kcmil152.0 mm²285 A0.56 V (0.23%)239.4 V0.92 V (0.38%)181.3 WDrop/Amp High
350 kcmil177.3 mm²310 A0.48 V (0.2%)239.5 V0.79 V (0.33%)155.4 WDrop/Amp High
400 kcmil202.7 mm²335 A0.42 V (0.17%)239.6 V0.69 V (0.29%)136.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.33 V (0.14%)239.7 V0.55 V (0.23%)108.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.28 V (0.12%)239.7 V0.46 V (0.19%)90.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.22 V (0.09%)239.8 V0.37 V (0.15%)72.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.17 V (0.07%)239.8 V0.28 V (0.12%)54.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 20 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 20 feet one-way at 240V (1-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 0.42V (0.17%) and delivers 239.6V at the load.

What size aluminum wire is required for 325 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 0.46V (0.19%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.