⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 100 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 0.75%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 1.99V (0.83%)
Voltage at Load End238.2 VLoss: 1.81 V (1019.7 W)
Power & Breaker (125%)135.1 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 100 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A176.53 V (73.55%)63.5 V291.19 V (121.33%)99369.6 WDrop/Amp High
12 AWG3.31 mm²20 A110.93 V (46.22%)129.1 V182.98 V (76.24%)62443.7 WDrop/Amp High
10 AWG5.26 mm²30 A69.81 V (29.09%)170.2 V115.15 V (47.98%)39294.4 WDrop/Amp High
8 AWG8.37 mm²50 A43.87 V (18.28%)196.1 V72.36 V (30.15%)24694.0 WDrop/Amp High
6 AWG13.3 mm²65 A27.61 V (11.5%)212.4 V45.54 V (18.97%)15540.5 WDrop/Amp High
4 AWG21.15 mm²85 A17.36 V (7.23%)222.6 V28.64 V (11.93%)9772.5 WDrop/Amp High
3 AWG26.67 mm²100 A13.77 V (5.74%)226.2 V22.71 V (9.46%)7749.9 WDrop/Amp High
2 AWG33.62 mm²115 A10.92 V (4.55%)229.1 V18.02 V (7.51%)6147.8 WDrop/Amp High
1 AWG42.41 mm²130 A8.66 V (3.61%)231.3 V14.28 V (5.95%)4873.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.86 V (2.86%)233.1 V11.32 V (4.72%)3864.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.45 V (2.27%)234.6 V8.98 V (3.74%)3065.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.32 V (1.8%)235.7 V7.12 V (2.97%)2431.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.43 V (1.43%)236.6 V5.65 V (2.35%)1928.1 WDrop/Amp High
250 kcmil126.7 mm²255 A2.9 V (1.21%)237.1 V4.78 V (1.99%)1631.3 WDrop/Amp High
300 kcmil152.0 mm²285 A2.42 V (1.01%)237.6 V3.98 V (1.66%)1359.8 WDrop/Amp High
350 kcmil177.3 mm²310 A2.07 V (0.86%)237.9 V3.42 V (1.42%)1165.8 WDrop/Amp High
400 kcmil202.7 mm²335 A1.81 V (0.75%)238.2 V2.99 V (1.24%)1019.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.45 V (0.6%)238.6 V2.39 V (1.0%)815.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.21 V (0.5%)238.8 V1.99 V (0.83%)679.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.97 V (0.4%)239.0 V1.59 V (0.66%)543.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.72 V (0.3%)239.3 V1.2 V (0.5%)407.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 100 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 100 feet one-way at 240V (3-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 1.81V (0.75%) and delivers 238.2V at the load.

What size aluminum wire is required for 325 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 1.99V (0.83%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.