🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 175 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 1.32%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 3.49V (1.45%)
Voltage at Load End236.8 VLoss: 3.17 V (1784.4 W)
Power & Breaker (125%)135.1 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A308.92 V (128.72%)0.0 V509.58 V (212.32%)173896.7 WDrop/Amp High
12 AWG3.31 mm²20 A194.13 V (80.89%)45.9 V320.22 V (133.42%)109276.5 WDrop/Amp High
10 AWG5.26 mm²30 A122.16 V (50.9%)117.8 V201.51 V (83.96%)68765.2 WDrop/Amp High
8 AWG8.37 mm²50 A76.77 V (31.99%)163.2 V126.63 V (52.76%)43214.5 WDrop/Amp High
6 AWG13.3 mm²65 A48.31 V (20.13%)191.7 V79.69 V (33.21%)27195.9 WDrop/Amp High
4 AWG21.15 mm²85 A30.38 V (12.66%)209.6 V50.11 V (20.88%)17101.9 WDrop/Amp High
3 AWG26.67 mm²100 A24.09 V (10.04%)215.9 V39.74 V (16.56%)13562.2 WDrop/Amp High
2 AWG33.62 mm²115 A19.11 V (7.96%)220.9 V31.53 V (13.14%)10758.6 WDrop/Amp High
1 AWG42.41 mm²130 A15.15 V (6.31%)224.8 V24.99 V (10.41%)8528.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A12.01 V (5.01%)228.0 V19.82 V (8.26%)6762.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.53 V (3.97%)230.5 V15.72 V (6.55%)5364.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.56 V (3.15%)232.4 V12.47 V (5.2%)4254.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.99 V (2.5%)234.0 V9.89 V (4.12%)3374.1 WDrop/Amp High
250 kcmil126.7 mm²255 A5.07 V (2.11%)234.9 V8.37 V (3.49%)2854.8 WDrop/Amp High
300 kcmil152.0 mm²285 A4.23 V (1.76%)235.8 V6.97 V (2.91%)2379.6 WDrop/Amp High
350 kcmil177.3 mm²310 A3.62 V (1.51%)236.4 V5.98 V (2.49%)2040.1 WDrop/Amp High
400 kcmil202.7 mm²335 A3.17 V (1.32%)236.8 V5.23 V (2.18%)1784.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.54 V (1.06%)237.5 V4.18 V (1.74%)1427.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.11 V (0.88%)237.9 V3.49 V (1.45%)1189.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.69 V (0.7%)238.3 V2.79 V (1.16%)951.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.27 V (0.53%)238.7 V2.09 V (0.87%)713.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 175 feet one-way at 240V (3-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 3.17V (1.32%) and delivers 236.8V at the load.

What size aluminum wire is required for 325 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 3.49V (1.45%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.