325 Amp Wire Size at 150 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 1.13%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 2.99V (1.25%)
Voltage at Load End237.3 VLoss: 2.72 V (1529.5 W)
Power & Breaker (125%)135.1 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 150 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A264.79 V (110.33%)0.0 V436.78 V (181.99%)149054.3 WDrop/Amp High
12 AWG3.31 mm²20 A166.39 V (69.33%)73.6 V274.47 V (114.36%)93665.6 WDrop/Amp High
10 AWG5.26 mm²30 A104.71 V (43.63%)135.3 V172.72 V (71.97%)58941.6 WDrop/Amp High
8 AWG8.37 mm²50 A65.8 V (27.42%)174.2 V108.54 V (45.23%)37041.0 WDrop/Amp High
6 AWG13.3 mm²65 A41.41 V (17.25%)198.6 V68.31 V (28.46%)23310.8 WDrop/Amp High
4 AWG21.15 mm²85 A26.04 V (10.85%)214.0 V42.96 V (17.9%)14658.8 WDrop/Amp High
3 AWG26.67 mm²100 A20.65 V (8.6%)219.3 V34.06 V (14.19%)11624.8 WDrop/Amp High
2 AWG33.62 mm²115 A16.38 V (6.83%)223.6 V27.02 V (11.26%)9221.7 WDrop/Amp High
1 AWG42.41 mm²130 A12.99 V (5.41%)227.0 V21.42 V (8.93%)7310.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.3 V (4.29%)229.7 V16.98 V (7.08%)5796.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.17 V (3.4%)231.8 V13.47 V (5.61%)4597.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.48 V (2.7%)233.5 V10.69 V (4.45%)3647.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.14 V (2.14%)234.9 V8.47 V (3.53%)2892.1 WDrop/Amp High
250 kcmil126.7 mm²255 A4.35 V (1.81%)235.7 V7.17 V (2.99%)2447.0 WDrop/Amp High
300 kcmil152.0 mm²285 A3.62 V (1.51%)236.4 V5.98 V (2.49%)2039.7 WDrop/Amp High
350 kcmil177.3 mm²310 A3.11 V (1.29%)236.9 V5.12 V (2.14%)1748.6 WDrop/Amp High
400 kcmil202.7 mm²335 A2.72 V (1.13%)237.3 V4.48 V (1.87%)1529.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.17 V (0.91%)237.8 V3.59 V (1.49%)1223.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.81 V (0.75%)238.2 V2.99 V (1.25%)1019.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.45 V (0.6%)238.6 V2.39 V (1.0%)815.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.09 V (0.45%)238.9 V1.79 V (0.75%)611.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 150 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 150 feet one-way at 240V (3-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 2.72V (1.13%) and delivers 237.3V at the load.

What size aluminum wire is required for 325 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 2.99V (1.25%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.