🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 40 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 0.3%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 0.8V (0.33%)
Voltage at Load End239.3 VLoss: 0.72 V (407.9 W)
Power & Breaker (125%)135.1 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 40 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A70.61 V (29.42%)169.4 V116.47 V (48.53%)39747.8 WDrop/Amp High
12 AWG3.31 mm²20 A44.37 V (18.49%)195.6 V73.19 V (30.5%)24977.5 WDrop/Amp High
10 AWG5.26 mm²30 A27.92 V (11.63%)212.1 V46.06 V (19.19%)15717.8 WDrop/Amp High
8 AWG8.37 mm²50 A17.55 V (7.31%)222.5 V28.94 V (12.06%)9877.6 WDrop/Amp High
6 AWG13.3 mm²65 A11.04 V (4.6%)229.0 V18.22 V (7.59%)6216.2 WDrop/Amp High
4 AWG21.15 mm²85 A6.94 V (2.89%)233.1 V11.45 V (4.77%)3909.0 WDrop/Amp High
3 AWG26.67 mm²100 A5.51 V (2.29%)234.5 V9.08 V (3.78%)3099.9 WDrop/Amp High
2 AWG33.62 mm²115 A4.37 V (1.82%)235.6 V7.21 V (3.0%)2459.1 WDrop/Amp High
1 AWG42.41 mm²130 A3.46 V (1.44%)236.5 V5.71 V (2.38%)1949.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.75 V (1.14%)237.3 V4.53 V (1.89%)1545.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.18 V (0.91%)237.8 V3.59 V (1.5%)1226.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.73 V (0.72%)238.3 V2.85 V (1.19%)972.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.37 V (0.57%)238.6 V2.26 V (0.94%)771.2 WDrop/Amp High
250 kcmil126.7 mm²255 A1.16 V (0.48%)238.8 V1.91 V (0.8%)652.5 WDrop/Amp High
300 kcmil152.0 mm²285 A0.97 V (0.4%)239.0 V1.59 V (0.66%)543.9 WDrop/Amp High
350 kcmil177.3 mm²310 A0.83 V (0.35%)239.2 V1.37 V (0.57%)466.3 WDrop/Amp High
400 kcmil202.7 mm²335 A0.72 V (0.3%)239.3 V1.2 V (0.5%)407.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.58 V (0.24%)239.4 V0.96 V (0.4%)326.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.48 V (0.2%)239.5 V0.8 V (0.33%)272.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.39 V (0.16%)239.6 V0.64 V (0.27%)217.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.29 V (0.12%)239.7 V0.48 V (0.2%)163.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 40 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 40 feet one-way at 240V (3-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 0.72V (0.3%) and delivers 239.3V at the load.

What size aluminum wire is required for 325 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 0.8V (0.33%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.