🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 120 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 0.91%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 2.39V (1.0%)
Voltage at Load End237.8 VLoss: 2.17 V (1223.6 W)
Power & Breaker (125%)135.1 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 120 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A211.83 V (88.26%)28.2 V349.42 V (145.59%)119243.5 WDrop/Amp High
12 AWG3.31 mm²20 A133.11 V (55.46%)106.9 V219.58 V (91.49%)74932.5 WDrop/Amp High
10 AWG5.26 mm²30 A83.77 V (34.9%)156.2 V138.17 V (57.57%)47153.3 WDrop/Amp High
8 AWG8.37 mm²50 A52.64 V (21.93%)187.4 V86.83 V (36.18%)29632.8 WDrop/Amp High
6 AWG13.3 mm²65 A33.13 V (13.8%)206.9 V54.65 V (22.77%)18648.6 WDrop/Amp High
4 AWG21.15 mm²85 A20.83 V (8.68%)219.2 V34.36 V (14.32%)11727.0 WDrop/Amp High
3 AWG26.67 mm²100 A16.52 V (6.88%)223.5 V27.25 V (11.35%)9299.8 WDrop/Amp High
2 AWG33.62 mm²115 A13.11 V (5.46%)226.9 V21.62 V (9.01%)7377.3 WDrop/Amp High
1 AWG42.41 mm²130 A10.39 V (4.33%)229.6 V17.14 V (7.14%)5848.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.24 V (3.43%)231.8 V13.59 V (5.66%)4636.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.53 V (2.72%)233.5 V10.78 V (4.49%)3678.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.18 V (2.16%)234.8 V8.55 V (3.56%)2917.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.11 V (1.71%)235.9 V6.78 V (2.82%)2313.7 WDrop/Amp High
250 kcmil126.7 mm²255 A3.48 V (1.45%)236.5 V5.74 V (2.39%)1957.6 WDrop/Amp High
300 kcmil152.0 mm²285 A2.9 V (1.21%)237.1 V4.78 V (1.99%)1631.8 WDrop/Amp High
350 kcmil177.3 mm²310 A2.49 V (1.04%)237.5 V4.1 V (1.71%)1398.9 WDrop/Amp High
400 kcmil202.7 mm²335 A2.17 V (0.91%)237.8 V3.59 V (1.49%)1223.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.74 V (0.72%)238.3 V2.87 V (1.2%)978.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.45 V (0.6%)238.6 V2.39 V (1.0%)815.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.16 V (0.48%)238.8 V1.91 V (0.8%)652.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.87 V (0.36%)239.1 V1.43 V (0.6%)489.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 120 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 120 feet one-way at 240V (3-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 2.17V (0.91%) and delivers 237.8V at the load.

What size aluminum wire is required for 325 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 2.39V (1.0%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.