🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 1000 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 2.52%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 11.95V (2.49%)
Voltage at Load End467.9 VLoss: 12.08 V (6799.0 W)
Power & Breaker (125%)270.2 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 1000 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1765.26 V (367.76%)0.0 V2911.86 V (606.64%)993695.6 WDrop/Amp High
12 AWG3.31 mm²20 A1109.29 V (231.1%)0.0 V1829.81 V (381.21%)624437.1 WDrop/Amp High
10 AWG5.26 mm²30 A698.05 V (145.43%)0.0 V1151.46 V (239.89%)392944.3 WDrop/Amp High
8 AWG8.37 mm²50 A438.68 V (91.39%)41.3 V723.62 V (150.75%)246939.9 WDrop/Amp High
6 AWG13.3 mm²65 A276.07 V (57.51%)203.9 V455.39 V (94.87%)155405.0 WDrop/Amp High
4 AWG21.15 mm²85 A173.61 V (36.17%)306.4 V286.37 V (59.66%)97725.1 WDrop/Amp High
3 AWG26.67 mm²100 A137.67 V (28.68%)342.3 V227.1 V (47.31%)77498.6 WDrop/Amp High
2 AWG33.62 mm²115 A109.21 V (22.75%)370.8 V180.15 V (37.53%)61477.9 WDrop/Amp High
1 AWG42.41 mm²130 A86.58 V (18.04%)393.4 V142.81 V (29.75%)48735.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A68.64 V (14.3%)411.4 V113.23 V (23.59%)38640.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A54.45 V (11.34%)425.5 V89.82 V (18.71%)30652.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A43.19 V (9.0%)436.8 V71.25 V (14.84%)24313.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A34.25 V (7.14%)445.7 V56.5 V (11.77%)19280.7 WDrop/Amp High
250 kcmil126.7 mm²255 A28.98 V (6.04%)451.0 V47.8 V (9.96%)16313.2 WDrop/Amp High
300 kcmil152.0 mm²285 A24.16 V (5.03%)455.8 V39.85 V (8.3%)13597.9 WDrop/Amp High
350 kcmil177.3 mm²310 A20.71 V (4.31%)459.3 V34.16 V (7.12%)11657.6 WDrop/Amp High
400 kcmil202.7 mm²335 A18.11 V (3.77%)461.9 V29.88 V (6.22%)10196.8 W~ ≤5%
500 kcmil253.4 mm²380 A14.49 V (3.02%)465.5 V23.9 V (4.98%)8156.6 W~ ≤5%
600 kcmil304.0 mm²420 A12.08 V (2.52%)467.9 V19.92 V (4.15%)6799.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A9.66 V (2.01%)470.3 V15.94 V (3.32%)5439.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A7.25 V (1.51%)472.8 V11.95 V (2.49%)4079.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 1000 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 1000 feet one-way at 480V (3-Phase), you need 600 kcmil copper wire. This produces a voltage drop of 12.08V (2.52%) and delivers 467.9V at the load.

What size aluminum wire is required for 325 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 11.95V (2.49%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.