⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 150 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 1.31%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 2.99V (1.44%)
Voltage at Load End205.3 VLoss: 2.72 V (1529.5 W)
Power & Breaker (125%)117.09 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 150 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A264.79 V (127.3%)0.0 V436.78 V (209.99%)149054.3 WDrop/Amp High
12 AWG3.31 mm²20 A166.39 V (80.0%)41.6 V274.47 V (131.96%)93665.6 WDrop/Amp High
10 AWG5.26 mm²30 A104.71 V (50.34%)103.3 V172.72 V (83.04%)58941.6 WDrop/Amp High
8 AWG8.37 mm²50 A65.8 V (31.64%)142.2 V108.54 V (52.18%)37041.0 WDrop/Amp High
6 AWG13.3 mm²65 A41.41 V (19.91%)166.6 V68.31 V (32.84%)23310.8 WDrop/Amp High
4 AWG21.15 mm²85 A26.04 V (12.52%)182.0 V42.96 V (20.65%)14658.8 WDrop/Amp High
3 AWG26.67 mm²100 A20.65 V (9.93%)187.3 V34.06 V (16.38%)11624.8 WDrop/Amp High
2 AWG33.62 mm²115 A16.38 V (7.88%)191.6 V27.02 V (12.99%)9221.7 WDrop/Amp High
1 AWG42.41 mm²130 A12.99 V (6.24%)195.0 V21.42 V (10.3%)7310.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.3 V (4.95%)197.7 V16.98 V (8.17%)5796.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.17 V (3.93%)199.8 V13.47 V (6.48%)4597.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.48 V (3.11%)201.5 V10.69 V (5.14%)3647.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.14 V (2.47%)202.9 V8.47 V (4.07%)2892.1 WDrop/Amp High
250 kcmil126.7 mm²255 A4.35 V (2.09%)203.7 V7.17 V (3.45%)2447.0 WDrop/Amp High
300 kcmil152.0 mm²285 A3.62 V (1.74%)204.4 V5.98 V (2.87%)2039.7 WDrop/Amp High
350 kcmil177.3 mm²310 A3.11 V (1.49%)204.9 V5.12 V (2.46%)1748.6 WDrop/Amp High
400 kcmil202.7 mm²335 A2.72 V (1.31%)205.3 V4.48 V (2.15%)1529.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.17 V (1.04%)205.8 V3.59 V (1.72%)1223.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.81 V (0.87%)206.2 V2.99 V (1.44%)1019.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.45 V (0.7%)206.6 V2.39 V (1.15%)815.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.09 V (0.52%)206.9 V1.79 V (0.86%)611.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 150 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 150 feet one-way at 208V (3-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 2.72V (1.31%) and delivers 205.3V at the load.

What size aluminum wire is required for 325 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 2.99V (1.44%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.