🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 80 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 0.7%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 1.59V (0.77%)
Voltage at Load End206.6 VLoss: 1.45 V (815.7 W)
Power & Breaker (125%)117.09 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 80 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A141.22 V (67.89%)66.8 V232.95 V (111.99%)79495.6 WDrop/Amp High
12 AWG3.31 mm²20 A88.74 V (42.66%)119.3 V146.38 V (70.38%)49955.0 WDrop/Amp High
10 AWG5.26 mm²30 A55.84 V (26.85%)152.2 V92.12 V (44.29%)31435.5 WDrop/Amp High
8 AWG8.37 mm²50 A35.09 V (16.87%)172.9 V57.89 V (27.83%)19755.2 WDrop/Amp High
6 AWG13.3 mm²65 A22.09 V (10.62%)185.9 V36.43 V (17.51%)12432.4 WDrop/Amp High
4 AWG21.15 mm²85 A13.89 V (6.68%)194.1 V22.91 V (11.01%)7818.0 WDrop/Amp High
3 AWG26.67 mm²100 A11.01 V (5.3%)197.0 V18.17 V (8.73%)6199.9 WDrop/Amp High
2 AWG33.62 mm²115 A8.74 V (4.2%)199.3 V14.41 V (6.93%)4918.2 WDrop/Amp High
1 AWG42.41 mm²130 A6.93 V (3.33%)201.1 V11.42 V (5.49%)3898.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.49 V (2.64%)202.5 V9.06 V (4.35%)3091.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.36 V (2.09%)203.6 V7.19 V (3.45%)2452.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.46 V (1.66%)204.5 V5.7 V (2.74%)1945.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.74 V (1.32%)205.3 V4.52 V (2.17%)1542.5 WDrop/Amp High
250 kcmil126.7 mm²255 A2.32 V (1.11%)205.7 V3.82 V (1.84%)1305.1 WDrop/Amp High
300 kcmil152.0 mm²285 A1.93 V (0.93%)206.1 V3.19 V (1.53%)1087.8 WDrop/Amp High
350 kcmil177.3 mm²310 A1.66 V (0.8%)206.3 V2.73 V (1.31%)932.6 WDrop/Amp High
400 kcmil202.7 mm²335 A1.45 V (0.7%)206.6 V2.39 V (1.15%)815.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.16 V (0.56%)206.8 V1.91 V (0.92%)652.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.97 V (0.46%)207.0 V1.59 V (0.77%)543.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.77 V (0.37%)207.2 V1.28 V (0.61%)435.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.58 V (0.28%)207.4 V0.96 V (0.46%)326.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 80 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 80 feet one-way at 208V (3-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 1.45V (0.7%) and delivers 206.6V at the load.

What size aluminum wire is required for 325 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 1.59V (0.77%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.