🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 120 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 1.05%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 2.39V (1.15%)
Voltage at Load End205.8 VLoss: 2.17 V (1223.6 W)
Power & Breaker (125%)117.09 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 120 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A211.83 V (101.84%)0.0 V349.42 V (167.99%)119243.5 WDrop/Amp High
12 AWG3.31 mm²20 A133.11 V (64.0%)74.9 V219.58 V (105.57%)74932.5 WDrop/Amp High
10 AWG5.26 mm²30 A83.77 V (40.27%)124.2 V138.17 V (66.43%)47153.3 WDrop/Amp High
8 AWG8.37 mm²50 A52.64 V (25.31%)155.4 V86.83 V (41.75%)29632.8 WDrop/Amp High
6 AWG13.3 mm²65 A33.13 V (15.93%)174.9 V54.65 V (26.27%)18648.6 WDrop/Amp High
4 AWG21.15 mm²85 A20.83 V (10.02%)187.2 V34.36 V (16.52%)11727.0 WDrop/Amp High
3 AWG26.67 mm²100 A16.52 V (7.94%)191.5 V27.25 V (13.1%)9299.8 WDrop/Amp High
2 AWG33.62 mm²115 A13.11 V (6.3%)194.9 V21.62 V (10.39%)7377.3 WDrop/Amp High
1 AWG42.41 mm²130 A10.39 V (4.99%)197.6 V17.14 V (8.24%)5848.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.24 V (3.96%)199.8 V13.59 V (6.53%)4636.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.53 V (3.14%)201.5 V10.78 V (5.18%)3678.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.18 V (2.49%)202.8 V8.55 V (4.11%)2917.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.11 V (1.98%)203.9 V6.78 V (3.26%)2313.7 WDrop/Amp High
250 kcmil126.7 mm²255 A3.48 V (1.67%)204.5 V5.74 V (2.76%)1957.6 WDrop/Amp High
300 kcmil152.0 mm²285 A2.9 V (1.39%)205.1 V4.78 V (2.3%)1631.8 WDrop/Amp High
350 kcmil177.3 mm²310 A2.49 V (1.19%)205.5 V4.1 V (1.97%)1398.9 WDrop/Amp High
400 kcmil202.7 mm²335 A2.17 V (1.05%)205.8 V3.59 V (1.72%)1223.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.74 V (0.84%)206.3 V2.87 V (1.38%)978.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.45 V (0.7%)206.6 V2.39 V (1.15%)815.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.16 V (0.56%)206.8 V1.91 V (0.92%)652.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.87 V (0.42%)207.1 V1.43 V (0.69%)489.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 120 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 120 feet one-way at 208V (3-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 2.17V (1.05%) and delivers 205.8V at the load.

What size aluminum wire is required for 325 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 2.39V (1.15%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.