🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 600 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.17V (3.45%)
Voltage at Load End202.2 VLoss: 5.8 V (3263.5 W)
Power & Breaker (125%)117.09 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 600 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1059.16 V (509.21%)0.0 V1747.12 V (839.96%)596217.4 WDrop/Amp High
12 AWG3.31 mm²20 A665.57 V (319.99%)0.0 V1097.89 V (527.83%)374662.3 WDrop/Amp High
10 AWG5.26 mm²30 A418.83 V (201.36%)0.0 V690.87 V (332.15%)235766.6 WDrop/Amp High
8 AWG8.37 mm²50 A263.21 V (126.54%)0.0 V434.17 V (208.74%)148163.9 WDrop/Amp High
6 AWG13.3 mm²65 A165.64 V (79.64%)42.4 V273.23 V (131.36%)93243.0 WDrop/Amp High
4 AWG21.15 mm²85 A104.16 V (50.08%)103.8 V171.82 V (82.61%)58635.1 WDrop/Amp High
3 AWG26.67 mm²100 A82.6 V (39.71%)125.4 V136.26 V (65.51%)46499.1 WDrop/Amp High
2 AWG33.62 mm²115 A65.53 V (31.5%)142.5 V108.09 V (51.97%)36886.7 WDrop/Amp High
1 AWG42.41 mm²130 A51.95 V (24.97%)156.1 V85.69 V (41.2%)29241.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A41.19 V (19.8%)166.8 V67.94 V (32.66%)23184.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A32.67 V (15.71%)175.3 V53.89 V (25.91%)18391.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A25.92 V (12.46%)182.1 V42.75 V (20.55%)14588.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A20.55 V (9.88%)187.4 V33.9 V (16.3%)11568.4 WDrop/Amp High
250 kcmil126.7 mm²255 A17.39 V (8.36%)190.6 V28.68 V (13.79%)9787.9 WDrop/Amp High
300 kcmil152.0 mm²285 A14.49 V (6.97%)193.5 V23.91 V (11.49%)8158.8 WDrop/Amp High
350 kcmil177.3 mm²310 A12.43 V (5.97%)195.6 V20.5 V (9.85%)6994.5 WDrop/Amp High
400 kcmil202.7 mm²335 A10.87 V (5.23%)197.1 V17.93 V (8.62%)6118.1 WDrop/Amp High
500 kcmil253.4 mm²380 A8.69 V (4.18%)199.3 V14.34 V (6.89%)4894.0 W~ ≤5%
600 kcmil304.0 mm²420 A7.25 V (3.48%)200.8 V11.95 V (5.75%)4079.4 W~ ≤5%
750 kcmil380.0 mm²475 A5.8 V (2.79%)202.2 V9.56 V (4.6%)3263.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A4.35 V (2.09%)203.7 V7.17 V (3.45%)2447.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 600 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 600 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 5.8V (2.79%) and delivers 202.2V at the load.

What size aluminum wire is required for 325 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.17V (3.45%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.