⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 275 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.71%
Aluminum Wire (≤3% Drop)6 AWGDrop: 13.49V (2.81%)
Voltage at Load End467.0 VLoss: 12.99 V (787.6 W)
Power & Breaker (125%)29.1 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 275 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A52.28 V (10.89%)427.7 V86.24 V (17.97%)3169.2 WDrop/Amp High
12 AWG3.31 mm²20 A32.85 V (6.84%)447.1 V54.19 V (11.29%)1991.5 WDrop/Amp High
10 AWG5.26 mm²30 A20.67 V (4.31%)459.3 V34.1 V (7.1%)1253.2 WDrop/Amp High
8 AWG8.37 mm²50 A12.99 V (2.71%)467.0 V21.43 V (4.46%)787.6 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A8.18 V (1.7%)471.8 V13.49 V (2.81%)495.6 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A5.14 V (1.07%)474.9 V8.48 V (1.77%)311.7 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A4.08 V (0.85%)475.9 V6.73 V (1.4%)247.2 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A3.23 V (0.67%)476.8 V5.34 V (1.11%)196.1 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.56 V (0.53%)477.4 V4.23 V (0.88%)155.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.03 V (0.42%)478.0 V3.35 V (0.7%)123.2 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.61 V (0.34%)478.4 V2.66 V (0.55%)97.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.28 V (0.27%)478.7 V2.11 V (0.44%)77.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.01 V (0.21%)479.0 V1.67 V (0.35%)61.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.86 V (0.18%)479.1 V1.42 V (0.29%)52.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.72 V (0.15%)479.3 V1.18 V (0.25%)43.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.61 V (0.13%)479.4 V1.01 V (0.21%)37.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.54 V (0.11%)479.5 V0.88 V (0.18%)32.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.43 V (0.09%)479.6 V0.71 V (0.15%)26.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.36 V (0.07%)479.6 V0.59 V (0.12%)21.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.29 V (0.06%)479.7 V0.47 V (0.1%)17.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.21 V (0.04%)479.8 V0.35 V (0.07%)13.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 275 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 275 feet one-way at 480V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 12.99V (2.71%) and delivers 467.0V at the load.

What size aluminum wire is required for 35 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 13.49V (2.81%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.