⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 450 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 2.54%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 5.49V (2.64%)
Voltage at Load End202.7 VLoss: 5.29 V (320.8 W)
Power & Breaker (125%)12.61 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 450 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A85.55 V (41.13%)122.5 V141.11 V (67.84%)5186.0 WDrop/Amp High
12 AWG3.31 mm²20 A53.76 V (25.85%)154.2 V88.68 V (42.63%)3258.9 WDrop/Amp High
10 AWG5.26 mm²30 A33.83 V (16.26%)174.2 V55.8 V (26.83%)2050.8 WDrop/Amp High
8 AWG8.37 mm²50 A21.26 V (10.22%)186.7 V35.07 V (16.86%)1288.8 WDrop/Amp High
6 AWG13.3 mm²65 A13.38 V (6.43%)194.6 V22.07 V (10.61%)811.0 WDrop/Amp High
4 AWG21.15 mm²85 A8.41 V (4.04%)199.6 V13.88 V (6.67%)510.0 W~ ≤5%
3 AWG26.67 mm²100 A6.67 V (3.21%)201.3 V11.01 V (5.29%)404.5 W~ ≤5%
2 AWG33.62 mm²115 A5.29 V (2.54%)202.7 V8.73 V (4.2%)320.8 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A4.2 V (2.02%)203.8 V6.92 V (3.33%)254.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A3.33 V (1.6%)204.7 V5.49 V (2.64%)201.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.64 V (1.27%)205.4 V4.35 V (2.09%)160.0 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.09 V (1.01%)205.9 V3.45 V (1.66%)126.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.66 V (0.8%)206.3 V2.74 V (1.32%)100.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.4 V (0.68%)206.6 V2.32 V (1.11%)85.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.17 V (0.56%)206.8 V1.93 V (0.93%)71.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.0 V (0.48%)207.0 V1.66 V (0.8%)60.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.88 V (0.42%)207.1 V1.45 V (0.7%)53.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.7 V (0.34%)207.3 V1.16 V (0.56%)42.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.59 V (0.28%)207.4 V0.97 V (0.46%)35.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.47 V (0.23%)207.5 V0.77 V (0.37%)28.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.35 V (0.17%)207.6 V0.58 V (0.28%)21.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 450 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 450 feet one-way at 208V (3-Phase), you need 2 AWG copper wire. This produces a voltage drop of 5.29V (2.54%) and delivers 202.7V at the load.

What size aluminum wire is required for 35 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 5.49V (2.64%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.