🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 250 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 1.88%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 4.96V (2.06%)
Voltage at Load End235.5 VLoss: 4.5 V (1576.6 W)
Power & Breaker (125%)84.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 250 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A548.79 V (228.66%)0.0 V905.24 V (377.18%)192075.3 WDrop/Amp High
12 AWG3.31 mm²20 A344.86 V (143.69%)0.0 V568.85 V (237.02%)120699.9 WDrop/Amp High
10 AWG5.26 mm²30 A217.01 V (90.42%)23.0 V357.97 V (149.15%)75953.7 WDrop/Amp High
8 AWG8.37 mm²50 A136.38 V (56.82%)103.6 V224.96 V (93.73%)47732.0 WDrop/Amp High
6 AWG13.3 mm²65 A85.83 V (35.76%)154.2 V141.57 V (58.99%)30038.8 WDrop/Amp High
4 AWG21.15 mm²85 A53.97 V (22.49%)186.0 V89.03 V (37.09%)18889.7 WDrop/Amp High
3 AWG26.67 mm²100 A42.8 V (17.83%)197.2 V70.6 V (29.42%)14980.0 WDrop/Amp High
2 AWG33.62 mm²115 A33.95 V (14.15%)206.0 V56.01 V (23.34%)11883.3 WDrop/Amp High
1 AWG42.41 mm²130 A26.92 V (11.21%)213.1 V44.4 V (18.5%)9420.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A21.34 V (8.89%)218.7 V35.2 V (14.67%)7469.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A16.93 V (7.05%)223.1 V27.92 V (11.63%)5924.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A13.43 V (5.59%)226.6 V22.15 V (9.23%)4699.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.65 V (4.44%)229.4 V17.56 V (7.32%)3726.8 WDrop/Amp High
250 kcmil126.7 mm²255 A9.01 V (3.75%)231.0 V14.86 V (6.19%)3153.2 WDrop/Amp High
300 kcmil152.0 mm²285 A7.51 V (3.13%)232.5 V12.39 V (5.16%)2628.4 WDrop/Amp High
350 kcmil177.3 mm²310 A6.44 V (2.68%)233.6 V10.62 V (4.42%)2253.3 WDrop/Amp High
400 kcmil202.7 mm²335 A5.63 V (2.35%)234.4 V9.29 V (3.87%)1971.0 WDrop/Amp High
500 kcmil253.4 mm²380 A4.5 V (1.88%)235.5 V7.43 V (3.1%)1576.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.75 V (1.56%)236.2 V6.19 V (2.58%)1314.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.0 V (1.25%)237.0 V4.96 V (2.06%)1051.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.25 V (0.94%)237.7 V3.72 V (1.55%)788.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 250 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 250 feet one-way at 240V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 4.5V (1.88%) and delivers 235.5V at the load.

What size aluminum wire is required for 350 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 4.96V (2.06%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.