375 Amp Wire Size at 275 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 0.96%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 5.06V (1.05%)
Voltage at Load End475.4 VLoss: 4.6 V (2986.3 W)
Power & Breaker (125%)311.77 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 275 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A560.13 V (116.69%)0.0 V923.96 V (192.49%)363816.1 WDrop/Amp High
12 AWG3.31 mm²20 A351.99 V (73.33%)128.0 V580.61 V (120.96%)228621.6 WDrop/Amp High
10 AWG5.26 mm²30 A221.5 V (46.15%)258.5 V365.37 V (76.12%)143866.4 WDrop/Amp High
8 AWG8.37 mm²50 A139.2 V (29.0%)340.8 V229.61 V (47.84%)90410.7 WDrop/Amp High
6 AWG13.3 mm²65 A87.6 V (18.25%)392.4 V144.5 V (30.1%)56897.6 WDrop/Amp High
4 AWG21.15 mm²85 A55.09 V (11.48%)424.9 V90.87 V (18.93%)35779.5 WDrop/Amp High
3 AWG26.67 mm²100 A43.68 V (9.1%)436.3 V72.06 V (15.01%)28374.1 WDrop/Amp High
2 AWG33.62 mm²115 A34.65 V (7.22%)445.3 V57.16 V (11.91%)22508.5 WDrop/Amp High
1 AWG42.41 mm²130 A27.47 V (5.72%)452.5 V45.32 V (9.44%)17843.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A21.78 V (4.54%)458.2 V35.93 V (7.49%)14147.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A17.28 V (3.6%)462.7 V28.5 V (5.94%)11222.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A13.71 V (2.86%)466.3 V22.61 V (4.71%)8901.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.87 V (2.26%)469.1 V17.93 V (3.73%)7059.1 WDrop/Amp High
250 kcmil126.7 mm²255 A9.2 V (1.92%)470.8 V15.17 V (3.16%)5972.7 WDrop/Amp High
300 kcmil152.0 mm²285 A7.66 V (1.6%)472.3 V12.64 V (2.63%)4978.5 WDrop/Amp High
350 kcmil177.3 mm²310 A6.57 V (1.37%)473.4 V10.84 V (2.26%)4268.1 WDrop/Amp High
400 kcmil202.7 mm²335 A5.75 V (1.2%)474.3 V9.48 V (1.98%)3733.3 WDrop/Amp High
500 kcmil253.4 mm²380 A4.6 V (0.96%)475.4 V7.58 V (1.58%)2986.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.83 V (0.8%)476.2 V6.32 V (1.32%)2489.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.07 V (0.64%)476.9 V5.06 V (1.05%)1991.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.3 V (0.48%)477.7 V3.79 V (0.79%)1493.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 275 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 275 feet one-way at 480V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 4.6V (0.96%) and delivers 475.4V at the load.

What size aluminum wire is required for 375 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 5.06V (1.05%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.