🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 350 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.81%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.83V (2.32%)
Voltage at Load End202.1 VLoss: 5.85 V (3800.8 W)
Power & Breaker (125%)135.1 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 350 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A712.89 V (342.74%)0.0 V1175.94 V (565.36%)463038.6 WDrop/Amp High
12 AWG3.31 mm²20 A447.98 V (215.38%)0.0 V738.96 V (355.27%)290972.9 WDrop/Amp High
10 AWG5.26 mm²30 A281.91 V (135.53%)0.0 V465.01 V (223.56%)183102.7 WDrop/Amp High
8 AWG8.37 mm²50 A177.16 V (85.17%)30.8 V292.23 V (140.49%)115068.1 WDrop/Amp High
6 AWG13.3 mm²65 A111.49 V (53.6%)96.5 V183.91 V (88.42%)72415.1 WDrop/Amp High
4 AWG21.15 mm²85 A70.11 V (33.71%)137.9 V115.65 V (55.6%)45537.6 WDrop/Amp High
3 AWG26.67 mm²100 A55.6 V (26.73%)152.4 V91.71 V (44.09%)36112.5 WDrop/Amp High
2 AWG33.62 mm²115 A44.11 V (21.2%)163.9 V72.75 V (34.98%)28647.2 WDrop/Amp High
1 AWG42.41 mm²130 A34.96 V (16.81%)173.0 V57.67 V (27.73%)22709.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A27.72 V (13.33%)180.3 V45.73 V (21.98%)18005.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A21.99 V (10.57%)186.0 V36.27 V (17.44%)14283.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A17.44 V (8.39%)190.6 V28.77 V (13.83%)11329.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A13.83 V (6.65%)194.2 V22.82 V (10.97%)8984.3 WDrop/Amp High
250 kcmil126.7 mm²255 A11.7 V (5.63%)196.3 V19.31 V (9.28%)7601.6 WDrop/Amp High
300 kcmil152.0 mm²285 A9.76 V (4.69%)198.2 V16.09 V (7.74%)6336.3 WDrop/Amp High
350 kcmil177.3 mm²310 A8.36 V (4.02%)199.6 V13.8 V (6.63%)5432.2 WDrop/Amp High
400 kcmil202.7 mm²335 A7.32 V (3.52%)200.7 V12.07 V (5.8%)4751.5 WDrop/Amp High
500 kcmil253.4 mm²380 A5.85 V (2.81%)202.1 V9.65 V (4.64%)3800.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A4.88 V (2.35%)203.1 V8.05 V (3.87%)3168.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.9 V (1.88%)204.1 V6.44 V (3.09%)2534.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.93 V (1.41%)205.1 V4.83 V (2.32%)1900.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 350 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 350 feet one-way at 208V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 5.85V (2.81%) and delivers 202.1V at the load.

What size aluminum wire is required for 375 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.83V (2.32%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.