🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 100 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.61%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.8V (0.75%)
Voltage at Load End238.5 VLoss: 1.46 V (620.1 W)
Power & Breaker (125%)102.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 100 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A266.55 V (111.06%)0.0 V439.69 V (183.2%)113285.2 WDrop/Amp High
12 AWG3.31 mm²20 A167.5 V (69.79%)72.5 V276.3 V (115.12%)71188.3 WDrop/Amp High
10 AWG5.26 mm²30 A105.41 V (43.92%)134.6 V173.87 V (72.45%)44797.2 WDrop/Amp High
8 AWG8.37 mm²50 A66.24 V (27.6%)173.8 V109.27 V (45.53%)28152.1 WDrop/Amp High
6 AWG13.3 mm²65 A41.69 V (17.37%)198.3 V68.76 V (28.65%)17716.8 WDrop/Amp High
4 AWG21.15 mm²85 A26.21 V (10.92%)213.8 V43.24 V (18.02%)11141.1 WDrop/Amp High
3 AWG26.67 mm²100 A20.79 V (8.66%)219.2 V34.29 V (14.29%)8835.1 WDrop/Amp High
2 AWG33.62 mm²115 A16.49 V (6.87%)223.5 V27.2 V (11.33%)7008.7 WDrop/Amp High
1 AWG42.41 mm²130 A13.07 V (5.45%)226.9 V21.56 V (8.99%)5556.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.37 V (4.32%)229.6 V17.1 V (7.12%)4405.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.22 V (3.43%)231.8 V13.56 V (5.65%)3494.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.52 V (2.72%)233.5 V10.76 V (4.48%)2771.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.17 V (2.15%)234.8 V8.53 V (3.55%)2198.1 WDrop/Amp High
250 kcmil126.7 mm²255 A4.38 V (1.82%)235.6 V7.22 V (3.01%)1859.8 WDrop/Amp High
300 kcmil152.0 mm²285 A3.65 V (1.52%)236.4 V6.02 V (2.51%)1550.2 WDrop/Amp High
350 kcmil177.3 mm²310 A3.13 V (1.3%)236.9 V5.16 V (2.15%)1329.0 WDrop/Amp High
400 kcmil202.7 mm²335 A2.74 V (1.14%)237.3 V4.51 V (1.88%)1162.5 WDrop/Amp High
500 kcmil253.4 mm²380 A2.19 V (0.91%)237.8 V3.61 V (1.5%)929.9 WDrop/Amp High
600 kcmil304.0 mm²420 A1.82 V (0.76%)238.2 V3.01 V (1.25%)775.1 WDrop/Amp High
750 kcmil380.0 mm²475 A1.46 V (0.61%)238.5 V2.41 V (1.0%)620.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.09 V (0.46%)238.9 V1.8 V (0.75%)465.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 100 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 100 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.46V (0.61%) and delivers 238.5V at the load.

What size aluminum wire is required for 425 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.8V (0.75%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.