🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 75 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.46%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.35V (0.56%)
Voltage at Load End238.9 VLoss: 1.09 V (465.1 W)
Power & Breaker (125%)102.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 75 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A199.92 V (83.3%)40.1 V329.77 V (137.4%)84963.9 WDrop/Amp High
12 AWG3.31 mm²20 A125.63 V (52.34%)114.4 V207.22 V (86.34%)53391.2 WDrop/Amp High
10 AWG5.26 mm²30 A79.05 V (32.94%)160.9 V130.4 V (54.33%)33597.9 WDrop/Amp High
8 AWG8.37 mm²50 A49.68 V (20.7%)190.3 V81.95 V (34.15%)21114.1 WDrop/Amp High
6 AWG13.3 mm²65 A31.26 V (13.03%)208.7 V51.57 V (21.49%)13287.6 WDrop/Amp High
4 AWG21.15 mm²85 A19.66 V (8.19%)220.3 V32.43 V (13.51%)8355.8 WDrop/Amp High
3 AWG26.67 mm²100 A15.59 V (6.5%)224.4 V25.72 V (10.72%)6626.4 WDrop/Amp High
2 AWG33.62 mm²115 A12.37 V (5.15%)227.6 V20.4 V (8.5%)5256.5 WDrop/Amp High
1 AWG42.41 mm²130 A9.8 V (4.09%)230.2 V16.17 V (6.74%)4167.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.77 V (3.24%)232.2 V12.82 V (5.34%)3303.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.17 V (2.57%)233.8 V10.17 V (4.24%)2620.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.89 V (2.04%)235.1 V8.07 V (3.36%)2078.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.88 V (1.62%)236.1 V6.4 V (2.67%)1648.6 WDrop/Amp High
250 kcmil126.7 mm²255 A3.28 V (1.37%)236.7 V5.41 V (2.26%)1394.8 WDrop/Amp High
300 kcmil152.0 mm²285 A2.74 V (1.14%)237.3 V4.51 V (1.88%)1162.7 WDrop/Amp High
350 kcmil177.3 mm²310 A2.35 V (0.98%)237.7 V3.87 V (1.61%)996.8 WDrop/Amp High
400 kcmil202.7 mm²335 A2.05 V (0.85%)237.9 V3.38 V (1.41%)871.9 WDrop/Amp High
500 kcmil253.4 mm²380 A1.64 V (0.68%)238.4 V2.71 V (1.13%)697.4 WDrop/Amp High
600 kcmil304.0 mm²420 A1.37 V (0.57%)238.6 V2.26 V (0.94%)581.3 WDrop/Amp High
750 kcmil380.0 mm²475 A1.09 V (0.46%)238.9 V1.81 V (0.75%)465.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.82 V (0.34%)239.2 V1.35 V (0.56%)348.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 75 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 75 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.09V (0.46%) and delivers 238.9V at the load.

What size aluminum wire is required for 425 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.35V (0.56%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.