🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 150 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.91%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.71V (1.13%)
Voltage at Load End237.8 VLoss: 2.19 V (930.1 W)
Power & Breaker (125%)102.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 150 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A399.83 V (166.6%)0.0 V659.53 V (274.81%)169927.8 WDrop/Amp High
12 AWG3.31 mm²20 A251.25 V (104.69%)0.0 V414.45 V (172.69%)106782.4 WDrop/Amp High
10 AWG5.26 mm²30 A158.11 V (65.88%)81.9 V260.8 V (108.67%)67195.8 WDrop/Amp High
8 AWG8.37 mm²50 A99.36 V (41.4%)140.6 V163.9 V (68.29%)42228.2 WDrop/Amp High
6 AWG13.3 mm²65 A62.53 V (26.05%)177.5 V103.15 V (42.98%)26575.2 WDrop/Amp High
4 AWG21.15 mm²85 A39.32 V (16.38%)200.7 V64.86 V (27.03%)16711.6 WDrop/Amp High
3 AWG26.67 mm²100 A31.18 V (12.99%)208.8 V51.44 V (21.43%)13252.7 WDrop/Amp High
2 AWG33.62 mm²115 A24.74 V (10.31%)215.3 V40.8 V (17.0%)10513.1 WDrop/Amp High
1 AWG42.41 mm²130 A19.61 V (8.17%)220.4 V32.35 V (13.48%)8334.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A15.55 V (6.48%)224.5 V25.65 V (10.69%)6607.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.33 V (5.14%)227.7 V20.34 V (8.48%)5241.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.78 V (4.08%)230.2 V16.14 V (6.72%)4157.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.76 V (3.23%)232.2 V12.8 V (5.33%)3297.1 WDrop/Amp High
250 kcmil126.7 mm²255 A6.56 V (2.73%)233.4 V10.83 V (4.51%)2789.7 WDrop/Amp High
300 kcmil152.0 mm²285 A5.47 V (2.28%)234.5 V9.03 V (3.76%)2325.3 WDrop/Amp High
350 kcmil177.3 mm²310 A4.69 V (1.95%)235.3 V7.74 V (3.22%)1993.5 WDrop/Amp High
400 kcmil202.7 mm²335 A4.1 V (1.71%)235.9 V6.77 V (2.82%)1743.7 WDrop/Amp High
500 kcmil253.4 mm²380 A3.28 V (1.37%)236.7 V5.41 V (2.26%)1394.8 WDrop/Amp High
600 kcmil304.0 mm²420 A2.74 V (1.14%)237.3 V4.51 V (1.88%)1162.7 WDrop/Amp High
750 kcmil380.0 mm²475 A2.19 V (0.91%)237.8 V3.61 V (1.5%)930.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.64 V (0.68%)238.4 V2.71 V (1.13%)697.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 150 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 150 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 2.19V (0.91%) and delivers 237.8V at the load.

What size aluminum wire is required for 425 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.71V (1.13%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.