425 Amp Wire Size at 125 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.76%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.26V (0.94%)
Voltage at Load End238.2 VLoss: 1.82 V (775.1 W)
Power & Breaker (125%)102.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 125 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A333.19 V (138.83%)0.0 V549.61 V (229.0%)141606.5 WDrop/Amp High
12 AWG3.31 mm²20 A209.38 V (87.24%)30.6 V345.37 V (143.91%)88985.4 WDrop/Amp High
10 AWG5.26 mm²30 A131.76 V (54.9%)108.2 V217.34 V (90.56%)55996.5 WDrop/Amp High
8 AWG8.37 mm²50 A82.8 V (34.5%)157.2 V136.58 V (56.91%)35190.2 WDrop/Amp High
6 AWG13.3 mm²65 A52.11 V (21.71%)187.9 V85.95 V (35.81%)22146.0 WDrop/Amp High
4 AWG21.15 mm²85 A32.77 V (13.65%)207.2 V54.05 V (22.52%)13926.3 WDrop/Amp High
3 AWG26.67 mm²100 A25.99 V (10.83%)214.0 V42.86 V (17.86%)11043.9 WDrop/Amp High
2 AWG33.62 mm²115 A20.61 V (8.59%)219.4 V34.0 V (14.17%)8760.9 WDrop/Amp High
1 AWG42.41 mm²130 A16.34 V (6.81%)223.7 V26.96 V (11.23%)6945.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A12.96 V (5.4%)227.0 V21.37 V (8.91%)5506.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.28 V (4.28%)229.7 V16.95 V (7.06%)4368.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.15 V (3.4%)231.8 V13.45 V (5.6%)3464.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.46 V (2.69%)233.5 V10.66 V (4.44%)2747.6 WDrop/Amp High
250 kcmil126.7 mm²255 A5.47 V (2.28%)234.5 V9.02 V (3.76%)2324.7 WDrop/Amp High
300 kcmil152.0 mm²285 A4.56 V (1.9%)235.4 V7.52 V (3.13%)1937.8 WDrop/Amp High
350 kcmil177.3 mm²310 A3.91 V (1.63%)236.1 V6.45 V (2.69%)1661.3 WDrop/Amp High
400 kcmil202.7 mm²335 A3.42 V (1.42%)236.6 V5.64 V (2.35%)1453.1 WDrop/Amp High
500 kcmil253.4 mm²380 A2.73 V (1.14%)237.3 V4.51 V (1.88%)1162.4 WDrop/Amp High
600 kcmil304.0 mm²420 A2.28 V (0.95%)237.7 V3.76 V (1.57%)968.9 WDrop/Amp High
750 kcmil380.0 mm²475 A1.82 V (0.76%)238.2 V3.01 V (1.25%)775.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.37 V (0.57%)238.6 V2.26 V (0.94%)581.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 125 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 125 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.82V (0.76%) and delivers 238.2V at the load.

What size aluminum wire is required for 425 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.26V (0.94%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.