⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 175 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.06%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.16V (1.32%)
Voltage at Load End237.4 VLoss: 2.55 V (1085.2 W)
Power & Breaker (125%)102.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A466.47 V (194.36%)0.0 V769.46 V (320.61%)198249.1 WDrop/Amp High
12 AWG3.31 mm²20 A293.13 V (122.14%)0.0 V483.52 V (201.47%)124579.5 WDrop/Amp High
10 AWG5.26 mm²30 A184.46 V (76.86%)55.5 V304.27 V (126.78%)78395.1 WDrop/Amp High
8 AWG8.37 mm²50 A115.92 V (48.3%)124.1 V191.21 V (79.67%)49266.2 WDrop/Amp High
6 AWG13.3 mm²65 A72.95 V (30.4%)167.0 V120.34 V (50.14%)31004.4 WDrop/Amp High
4 AWG21.15 mm²85 A45.87 V (19.11%)194.1 V75.67 V (31.53%)19496.8 WDrop/Amp High
3 AWG26.67 mm²100 A36.38 V (15.16%)203.6 V60.01 V (25.0%)15461.5 WDrop/Amp High
2 AWG33.62 mm²115 A28.86 V (12.02%)211.1 V47.6 V (19.84%)12265.3 WDrop/Amp High
1 AWG42.41 mm²130 A22.88 V (9.53%)217.1 V37.74 V (15.72%)9723.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A18.14 V (7.56%)221.9 V29.92 V (12.47%)7709.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A14.39 V (6.0%)225.6 V23.74 V (9.89%)6115.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A11.41 V (4.76%)228.6 V18.83 V (7.84%)4850.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A9.05 V (3.77%)230.9 V14.93 V (6.22%)3846.6 WDrop/Amp High
250 kcmil126.7 mm²255 A7.66 V (3.19%)232.3 V12.63 V (5.26%)3254.6 WDrop/Amp High
300 kcmil152.0 mm²285 A6.38 V (2.66%)233.6 V10.53 V (4.39%)2712.9 WDrop/Amp High
350 kcmil177.3 mm²310 A5.47 V (2.28%)234.5 V9.03 V (3.76%)2325.8 WDrop/Amp High
400 kcmil202.7 mm²335 A4.79 V (1.99%)235.2 V7.9 V (3.29%)2034.3 WDrop/Amp High
500 kcmil253.4 mm²380 A3.83 V (1.6%)236.2 V6.32 V (2.63%)1627.3 WDrop/Amp High
600 kcmil304.0 mm²420 A3.19 V (1.33%)236.8 V5.26 V (2.19%)1356.4 WDrop/Amp High
750 kcmil380.0 mm²475 A2.55 V (1.06%)237.4 V4.21 V (1.75%)1085.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.91 V (0.8%)238.1 V3.16 V (1.32%)813.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 175 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 2.55V (1.06%) and delivers 237.4V at the load.

What size aluminum wire is required for 425 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.16V (1.32%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.