🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 80 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.49%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.44V (0.6%)
Voltage at Load End238.8 VLoss: 1.17 V (496.1 W)
Power & Breaker (125%)102.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 80 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A213.24 V (88.85%)26.8 V351.75 V (146.56%)90628.2 WDrop/Amp High
12 AWG3.31 mm²20 A134.0 V (55.83%)106.0 V221.04 V (92.1%)56950.6 WDrop/Amp High
10 AWG5.26 mm²30 A84.32 V (35.14%)155.7 V139.1 V (57.96%)35837.8 WDrop/Amp High
8 AWG8.37 mm²50 A52.99 V (22.08%)187.0 V87.41 V (36.42%)22521.7 WDrop/Amp High
6 AWG13.3 mm²65 A33.35 V (13.9%)206.7 V55.01 V (22.92%)14173.4 WDrop/Amp High
4 AWG21.15 mm²85 A20.97 V (8.74%)219.0 V34.59 V (14.41%)8912.8 WDrop/Amp High
3 AWG26.67 mm²100 A16.63 V (6.93%)223.4 V27.43 V (11.43%)7068.1 WDrop/Amp High
2 AWG33.62 mm²115 A13.19 V (5.5%)226.8 V21.76 V (9.07%)5607.0 WDrop/Amp High
1 AWG42.41 mm²130 A10.46 V (4.36%)229.5 V17.25 V (7.19%)4444.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.29 V (3.46%)231.7 V13.68 V (5.7%)3524.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.58 V (2.74%)233.4 V10.85 V (4.52%)2795.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.22 V (2.17%)234.8 V8.61 V (3.59%)2217.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.14 V (1.72%)235.9 V6.83 V (2.84%)1758.5 WDrop/Amp High
250 kcmil126.7 mm²255 A3.5 V (1.46%)236.5 V5.77 V (2.41%)1487.8 WDrop/Amp High
300 kcmil152.0 mm²285 A2.92 V (1.22%)237.1 V4.81 V (2.01%)1240.2 WDrop/Amp High
350 kcmil177.3 mm²310 A2.5 V (1.04%)237.5 V4.13 V (1.72%)1063.2 WDrop/Amp High
400 kcmil202.7 mm²335 A2.19 V (0.91%)237.8 V3.61 V (1.5%)930.0 WDrop/Amp High
500 kcmil253.4 mm²380 A1.75 V (0.73%)238.2 V2.89 V (1.2%)743.9 WDrop/Amp High
600 kcmil304.0 mm²420 A1.46 V (0.61%)238.5 V2.41 V (1.0%)620.1 WDrop/Amp High
750 kcmil380.0 mm²475 A1.17 V (0.49%)238.8 V1.93 V (0.8%)496.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.88 V (0.36%)239.1 V1.44 V (0.6%)372.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 80 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 80 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.17V (0.49%) and delivers 238.8V at the load.

What size aluminum wire is required for 425 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.44V (0.6%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.