🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 40 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.24%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.72V (0.3%)
Voltage at Load End239.4 VLoss: 0.58 V (248.0 W)
Power & Breaker (125%)102.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 40 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A106.62 V (44.43%)133.4 V175.88 V (73.28%)45314.1 WDrop/Amp High
12 AWG3.31 mm²20 A67.0 V (27.92%)173.0 V110.52 V (46.05%)28475.3 WDrop/Amp High
10 AWG5.26 mm²30 A42.16 V (17.57%)197.8 V69.55 V (28.98%)17918.9 WDrop/Amp High
8 AWG8.37 mm²50 A26.5 V (11.04%)213.5 V43.71 V (18.21%)11260.8 WDrop/Amp High
6 AWG13.3 mm²65 A16.67 V (6.95%)223.3 V27.51 V (11.46%)7086.7 WDrop/Amp High
4 AWG21.15 mm²85 A10.49 V (4.37%)229.5 V17.3 V (7.21%)4456.4 WDrop/Amp High
3 AWG26.67 mm²100 A8.32 V (3.46%)231.7 V13.72 V (5.72%)3534.1 WDrop/Amp High
2 AWG33.62 mm²115 A6.6 V (2.75%)233.4 V10.88 V (4.53%)2803.5 WDrop/Amp High
1 AWG42.41 mm²130 A5.23 V (2.18%)234.8 V8.63 V (3.59%)2222.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.15 V (1.73%)235.9 V6.84 V (2.85%)1762.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.29 V (1.37%)236.7 V5.43 V (2.26%)1397.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.61 V (1.09%)237.4 V4.3 V (1.79%)1108.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.07 V (0.86%)237.9 V3.41 V (1.42%)879.2 WDrop/Amp High
250 kcmil126.7 mm²255 A1.75 V (0.73%)238.2 V2.89 V (1.2%)743.9 WDrop/Amp High
300 kcmil152.0 mm²285 A1.46 V (0.61%)238.5 V2.41 V (1.0%)620.1 WDrop/Amp High
350 kcmil177.3 mm²310 A1.25 V (0.52%)238.7 V2.06 V (0.86%)531.6 WDrop/Amp High
400 kcmil202.7 mm²335 A1.09 V (0.46%)238.9 V1.8 V (0.75%)465.0 WDrop/Amp High
500 kcmil253.4 mm²380 A0.88 V (0.36%)239.1 V1.44 V (0.6%)372.0 WDrop/Amp High
600 kcmil304.0 mm²420 A0.73 V (0.3%)239.3 V1.2 V (0.5%)310.0 WDrop/Amp High
750 kcmil380.0 mm²475 A0.58 V (0.24%)239.4 V0.96 V (0.4%)248.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.44 V (0.18%)239.6 V0.72 V (0.3%)186.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 40 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 40 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.58V (0.24%) and delivers 239.4V at the load.

What size aluminum wire is required for 425 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.72V (0.3%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.