⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 30 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.18%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.54V (0.23%)
Voltage at Load End239.6 VLoss: 0.44 V (186.0 W)
Power & Breaker (125%)102.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 30 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A79.97 V (33.32%)160.0 V131.91 V (54.96%)33985.6 WDrop/Amp High
12 AWG3.31 mm²20 A50.25 V (20.94%)189.7 V82.89 V (34.54%)21356.5 WDrop/Amp High
10 AWG5.26 mm²30 A31.62 V (13.18%)208.4 V52.16 V (21.73%)13439.2 WDrop/Amp High
8 AWG8.37 mm²50 A19.87 V (8.28%)220.1 V32.78 V (13.66%)8445.6 WDrop/Amp High
6 AWG13.3 mm²65 A12.51 V (5.21%)227.5 V20.63 V (8.6%)5315.0 WDrop/Amp High
4 AWG21.15 mm²85 A7.86 V (3.28%)232.1 V12.97 V (5.41%)3342.3 WDrop/Amp High
3 AWG26.67 mm²100 A6.24 V (2.6%)233.8 V10.29 V (4.29%)2650.5 WDrop/Amp High
2 AWG33.62 mm²115 A4.95 V (2.06%)235.1 V8.16 V (3.4%)2102.6 WDrop/Amp High
1 AWG42.41 mm²130 A3.92 V (1.63%)236.1 V6.47 V (2.7%)1666.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.11 V (1.3%)236.9 V5.13 V (2.14%)1321.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.47 V (1.03%)237.5 V4.07 V (1.7%)1048.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.96 V (0.82%)238.0 V3.23 V (1.34%)831.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.55 V (0.65%)238.4 V2.56 V (1.07%)659.4 WDrop/Amp High
250 kcmil126.7 mm²255 A1.31 V (0.55%)238.7 V2.17 V (0.9%)557.9 WDrop/Amp High
300 kcmil152.0 mm²285 A1.09 V (0.46%)238.9 V1.81 V (0.75%)465.1 WDrop/Amp High
350 kcmil177.3 mm²310 A0.94 V (0.39%)239.1 V1.55 V (0.64%)398.7 WDrop/Amp High
400 kcmil202.7 mm²335 A0.82 V (0.34%)239.2 V1.35 V (0.56%)348.7 WDrop/Amp High
500 kcmil253.4 mm²380 A0.66 V (0.27%)239.3 V1.08 V (0.45%)279.0 WDrop/Amp High
600 kcmil304.0 mm²420 A0.55 V (0.23%)239.5 V0.9 V (0.38%)232.5 WDrop/Amp High
750 kcmil380.0 mm²475 A0.44 V (0.18%)239.6 V0.72 V (0.3%)186.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.33 V (0.14%)239.7 V0.54 V (0.23%)139.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 30 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 30 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.44V (0.18%) and delivers 239.6V at the load.

What size aluminum wire is required for 425 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.54V (0.23%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.