⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 350 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.92%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.47V (1.14%)
Voltage at Load End475.6 VLoss: 4.42 V (3255.5 W)
Power & Breaker (125%)353.34 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 350 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A807.95 V (168.32%)0.0 V1332.74 V (277.65%)594747.4 WDrop/Amp High
12 AWG3.31 mm²20 A507.71 V (105.77%)0.0 V837.49 V (174.48%)373738.6 WDrop/Amp High
10 AWG5.26 mm²30 A319.49 V (66.56%)160.5 V527.01 V (109.79%)235185.3 WDrop/Amp High
8 AWG8.37 mm²50 A200.78 V (41.83%)279.2 V331.19 V (69.0%)147798.6 WDrop/Amp High
6 AWG13.3 mm²65 A126.36 V (26.32%)353.6 V208.43 V (43.42%)93013.1 WDrop/Amp High
4 AWG21.15 mm²85 A79.46 V (16.55%)400.5 V131.07 V (27.31%)58490.5 WDrop/Amp High
3 AWG26.67 mm²100 A63.01 V (13.13%)417.0 V103.94 V (21.65%)46384.5 WDrop/Amp High
2 AWG33.62 mm²115 A49.99 V (10.41%)430.0 V82.45 V (17.18%)36795.8 WDrop/Amp High
1 AWG42.41 mm²130 A39.63 V (8.26%)440.4 V65.36 V (13.62%)29169.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A31.42 V (6.55%)448.6 V51.82 V (10.8%)23127.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A24.92 V (5.19%)455.1 V41.11 V (8.56%)18346.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A19.77 V (4.12%)460.2 V32.61 V (6.79%)14552.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A15.68 V (3.27%)464.3 V25.86 V (5.39%)11539.9 WDrop/Amp High
250 kcmil126.7 mm²255 A13.26 V (2.76%)466.7 V21.88 V (4.56%)9763.8 WDrop/Amp High
300 kcmil152.0 mm²285 A11.06 V (2.3%)468.9 V18.24 V (3.8%)8138.6 WDrop/Amp High
350 kcmil177.3 mm²310 A9.48 V (1.97%)470.5 V15.64 V (3.26%)6977.3 WDrop/Amp High
400 kcmil202.7 mm²335 A8.29 V (1.73%)471.7 V13.68 V (2.85%)6103.0 WDrop/Amp High
500 kcmil253.4 mm²380 A6.63 V (1.38%)473.4 V10.94 V (2.28%)4881.9 WDrop/Amp High
600 kcmil304.0 mm²420 A5.53 V (1.15%)474.5 V9.12 V (1.9%)4069.3 WDrop/Amp High
750 kcmil380.0 mm²475 A4.42 V (0.92%)475.6 V7.29 V (1.52%)3255.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.32 V (0.69%)476.7 V5.47 V (1.14%)2441.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 350 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 350 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 4.42V (0.92%) and delivers 475.6V at the load.

What size aluminum wire is required for 425 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.47V (1.14%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.