🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 400 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.05%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.25V (1.3%)
Voltage at Load End474.9 VLoss: 5.05 V (3720.5 W)
Power & Breaker (125%)353.34 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 400 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A923.37 V (192.37%)0.0 V1523.13 V (317.32%)679711.3 WDrop/Amp High
12 AWG3.31 mm²20 A580.24 V (120.88%)0.0 V957.13 V (199.4%)427129.8 WDrop/Amp High
10 AWG5.26 mm²30 A365.13 V (76.07%)114.9 V602.3 V (125.48%)268783.2 WDrop/Amp High
8 AWG8.37 mm²50 A229.46 V (47.8%)250.5 V378.51 V (78.86%)168912.7 WDrop/Amp High
6 AWG13.3 mm²65 A144.41 V (30.08%)335.6 V238.2 V (49.63%)106300.7 WDrop/Amp High
4 AWG21.15 mm²85 A90.81 V (18.92%)389.2 V149.79 V (31.21%)66846.3 WDrop/Amp High
3 AWG26.67 mm²100 A72.01 V (15.0%)408.0 V118.79 V (24.75%)53010.9 WDrop/Amp High
2 AWG33.62 mm²115 A57.13 V (11.9%)422.9 V94.23 V (19.63%)42052.3 WDrop/Amp High
1 AWG42.41 mm²130 A45.29 V (9.43%)434.7 V74.7 V (15.56%)33336.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A35.91 V (7.48%)444.1 V59.23 V (12.34%)26431.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A28.48 V (5.93%)451.5 V46.98 V (9.79%)20966.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A22.59 V (4.71%)457.4 V37.27 V (7.76%)16631.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A17.92 V (3.73%)462.1 V29.55 V (6.16%)13188.4 WDrop/Amp High
250 kcmil126.7 mm²255 A15.16 V (3.16%)464.8 V25.0 V (5.21%)11158.6 WDrop/Amp High
300 kcmil152.0 mm²285 A12.64 V (2.63%)467.4 V20.84 V (4.34%)9301.3 WDrop/Amp High
350 kcmil177.3 mm²310 A10.83 V (2.26%)469.2 V17.87 V (3.72%)7974.1 WDrop/Amp High
400 kcmil202.7 mm²335 A9.48 V (1.97%)470.5 V15.63 V (3.26%)6974.8 WDrop/Amp High
500 kcmil253.4 mm²380 A7.58 V (1.58%)472.4 V12.5 V (2.6%)5579.3 WDrop/Amp High
600 kcmil304.0 mm²420 A6.32 V (1.32%)473.7 V10.42 V (2.17%)4650.7 WDrop/Amp High
750 kcmil380.0 mm²475 A5.05 V (1.05%)474.9 V8.34 V (1.74%)3720.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.79 V (0.79%)476.2 V6.25 V (1.3%)2790.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 400 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 400 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 5.05V (1.05%) and delivers 474.9V at the load.

What size aluminum wire is required for 425 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.25V (1.3%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.