425 Amp Wire Size at 60 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.32%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.94V (0.39%)
Voltage at Load End239.2 VLoss: 0.76 V (558.1 W)
Power & Breaker (125%)176.67 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 60 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A138.51 V (57.71%)101.5 V228.47 V (95.2%)101956.7 WDrop/Amp High
12 AWG3.31 mm²20 A87.04 V (36.27%)153.0 V143.57 V (59.82%)64069.5 WDrop/Amp High
10 AWG5.26 mm²30 A54.77 V (22.82%)185.2 V90.35 V (37.64%)40317.5 WDrop/Amp High
8 AWG8.37 mm²50 A34.42 V (14.34%)205.6 V56.78 V (23.66%)25336.9 WDrop/Amp High
6 AWG13.3 mm²65 A21.66 V (9.03%)218.3 V35.73 V (14.89%)15945.1 WDrop/Amp High
4 AWG21.15 mm²85 A13.62 V (5.68%)226.4 V22.47 V (9.36%)10026.9 WDrop/Amp High
3 AWG26.67 mm²100 A10.8 V (4.5%)229.2 V17.82 V (7.42%)7951.6 WDrop/Amp High
2 AWG33.62 mm²115 A8.57 V (3.57%)231.4 V14.13 V (5.89%)6307.9 WDrop/Amp High
1 AWG42.41 mm²130 A6.79 V (2.83%)233.2 V11.21 V (4.67%)5000.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.39 V (2.24%)234.6 V8.88 V (3.7%)3964.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.27 V (1.78%)235.7 V7.05 V (2.94%)3145.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.39 V (1.41%)236.6 V5.59 V (2.33%)2494.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.69 V (1.12%)237.3 V4.43 V (1.85%)1978.3 WDrop/Amp High
250 kcmil126.7 mm²255 A2.27 V (0.95%)237.7 V3.75 V (1.56%)1673.8 WDrop/Amp High
300 kcmil152.0 mm²285 A1.9 V (0.79%)238.1 V3.13 V (1.3%)1395.2 WDrop/Amp High
350 kcmil177.3 mm²310 A1.62 V (0.68%)238.4 V2.68 V (1.12%)1196.1 WDrop/Amp High
400 kcmil202.7 mm²335 A1.42 V (0.59%)238.6 V2.34 V (0.98%)1046.2 WDrop/Amp High
500 kcmil253.4 mm²380 A1.14 V (0.47%)238.9 V1.88 V (0.78%)836.9 WDrop/Amp High
600 kcmil304.0 mm²420 A0.95 V (0.39%)239.1 V1.56 V (0.65%)697.6 WDrop/Amp High
750 kcmil380.0 mm²475 A0.76 V (0.32%)239.2 V1.25 V (0.52%)558.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.57 V (0.24%)239.4 V0.94 V (0.39%)418.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 60 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 60 feet one-way at 240V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.76V (0.32%) and delivers 239.2V at the load.

What size aluminum wire is required for 425 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.94V (0.39%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.