🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 75 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.39%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.17V (0.49%)
Voltage at Load End239.1 VLoss: 0.95 V (697.6 W)
Power & Breaker (125%)176.67 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 75 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A173.13 V (72.14%)66.9 V285.59 V (118.99%)127445.9 WDrop/Amp High
12 AWG3.31 mm²20 A108.8 V (45.33%)131.2 V179.46 V (74.78%)80086.8 WDrop/Amp High
10 AWG5.26 mm²30 A68.46 V (28.53%)171.5 V112.93 V (47.05%)50396.8 WDrop/Amp High
8 AWG8.37 mm²50 A43.02 V (17.93%)197.0 V70.97 V (29.57%)31671.1 WDrop/Amp High
6 AWG13.3 mm²65 A27.08 V (11.28%)212.9 V44.66 V (18.61%)19931.4 WDrop/Amp High
4 AWG21.15 mm²85 A17.03 V (7.09%)223.0 V28.09 V (11.7%)12533.7 WDrop/Amp High
3 AWG26.67 mm²100 A13.5 V (5.63%)226.5 V22.27 V (9.28%)9939.5 WDrop/Amp High
2 AWG33.62 mm²115 A10.71 V (4.46%)229.3 V17.67 V (7.36%)7884.8 WDrop/Amp High
1 AWG42.41 mm²130 A8.49 V (3.54%)231.5 V14.01 V (5.84%)6250.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.73 V (2.81%)233.3 V11.11 V (4.63%)4955.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.34 V (2.23%)234.7 V8.81 V (3.67%)3931.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.24 V (1.77%)235.8 V6.99 V (2.91%)3118.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.36 V (1.4%)236.6 V5.54 V (2.31%)2472.8 WDrop/Amp High
250 kcmil126.7 mm²255 A2.84 V (1.18%)237.2 V4.69 V (1.95%)2092.2 WDrop/Amp High
300 kcmil152.0 mm²285 A2.37 V (0.99%)237.6 V3.91 V (1.63%)1744.0 WDrop/Amp High
350 kcmil177.3 mm²310 A2.03 V (0.85%)238.0 V3.35 V (1.4%)1495.1 WDrop/Amp High
400 kcmil202.7 mm²335 A1.78 V (0.74%)238.2 V2.93 V (1.22%)1307.8 WDrop/Amp High
500 kcmil253.4 mm²380 A1.42 V (0.59%)238.6 V2.34 V (0.98%)1046.1 WDrop/Amp High
600 kcmil304.0 mm²420 A1.18 V (0.49%)238.8 V1.95 V (0.81%)872.0 WDrop/Amp High
750 kcmil380.0 mm²475 A0.95 V (0.39%)239.1 V1.56 V (0.65%)697.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.71 V (0.3%)239.3 V1.17 V (0.49%)523.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 75 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 75 feet one-way at 240V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.95V (0.39%) and delivers 239.1V at the load.

What size aluminum wire is required for 425 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.17V (0.49%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.