⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 20 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.11%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.31V (0.13%)
Voltage at Load End239.7 VLoss: 0.25 V (186.0 W)
Power & Breaker (125%)176.67 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 20 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A46.17 V (19.24%)193.8 V76.16 V (31.73%)33985.6 WDrop/Amp High
12 AWG3.31 mm²20 A29.01 V (12.09%)211.0 V47.86 V (19.94%)21356.5 WDrop/Amp High
10 AWG5.26 mm²30 A18.26 V (7.61%)221.7 V30.12 V (12.55%)13439.2 WDrop/Amp High
8 AWG8.37 mm²50 A11.47 V (4.78%)228.5 V18.93 V (7.89%)8445.6 WDrop/Amp High
6 AWG13.3 mm²65 A7.22 V (3.01%)232.8 V11.91 V (4.96%)5315.0 WDrop/Amp High
4 AWG21.15 mm²85 A4.54 V (1.89%)235.5 V7.49 V (3.12%)3342.3 WDrop/Amp High
3 AWG26.67 mm²100 A3.6 V (1.5%)236.4 V5.94 V (2.47%)2650.5 WDrop/Amp High
2 AWG33.62 mm²115 A2.86 V (1.19%)237.1 V4.71 V (1.96%)2102.6 WDrop/Amp High
1 AWG42.41 mm²130 A2.26 V (0.94%)237.7 V3.74 V (1.56%)1666.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.8 V (0.75%)238.2 V2.96 V (1.23%)1321.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.42 V (0.59%)238.6 V2.35 V (0.98%)1048.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.13 V (0.47%)238.9 V1.86 V (0.78%)831.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.9 V (0.37%)239.1 V1.48 V (0.62%)659.4 WDrop/Amp High
250 kcmil126.7 mm²255 A0.76 V (0.32%)239.2 V1.25 V (0.52%)557.9 WDrop/Amp High
300 kcmil152.0 mm²285 A0.63 V (0.26%)239.4 V1.04 V (0.43%)465.1 WDrop/Amp High
350 kcmil177.3 mm²310 A0.54 V (0.23%)239.5 V0.89 V (0.37%)398.7 WDrop/Amp High
400 kcmil202.7 mm²335 A0.47 V (0.2%)239.5 V0.78 V (0.33%)348.7 WDrop/Amp High
500 kcmil253.4 mm²380 A0.38 V (0.16%)239.6 V0.63 V (0.26%)279.0 WDrop/Amp High
600 kcmil304.0 mm²420 A0.32 V (0.13%)239.7 V0.52 V (0.22%)232.5 WDrop/Amp High
750 kcmil380.0 mm²475 A0.25 V (0.11%)239.7 V0.42 V (0.17%)186.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.19 V (0.08%)239.8 V0.31 V (0.13%)139.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 20 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 20 feet one-way at 240V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.25V (0.11%) and delivers 239.7V at the load.

What size aluminum wire is required for 425 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.31V (0.13%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.