🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 150 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.79%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.34V (0.98%)
Voltage at Load End238.1 VLoss: 1.9 V (1395.2 W)
Power & Breaker (125%)176.67 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 150 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A346.26 V (144.28%)0.0 V571.17 V (237.99%)254891.7 WDrop/Amp High
12 AWG3.31 mm²20 A217.59 V (90.66%)22.4 V358.92 V (149.55%)160173.7 WDrop/Amp High
10 AWG5.26 mm²30 A136.93 V (57.05%)103.1 V225.86 V (94.11%)100793.7 WDrop/Amp High
8 AWG8.37 mm²50 A86.05 V (35.85%)154.0 V141.94 V (59.14%)63342.3 WDrop/Amp High
6 AWG13.3 mm²65 A54.15 V (22.56%)185.8 V89.33 V (37.22%)39862.8 WDrop/Amp High
4 AWG21.15 mm²85 A34.05 V (14.19%)205.9 V56.17 V (23.41%)25067.4 WDrop/Amp High
3 AWG26.67 mm²100 A27.01 V (11.25%)213.0 V44.55 V (18.56%)19879.1 WDrop/Amp High
2 AWG33.62 mm²115 A21.42 V (8.93%)218.6 V35.34 V (14.72%)15769.6 WDrop/Amp High
1 AWG42.41 mm²130 A16.98 V (7.08%)223.0 V28.01 V (11.67%)12501.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.46 V (5.61%)226.5 V22.21 V (9.25%)9911.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.68 V (4.45%)229.3 V17.62 V (7.34%)7862.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.47 V (3.53%)231.5 V13.98 V (5.82%)6236.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.72 V (2.8%)233.3 V11.08 V (4.62%)4945.7 WDrop/Amp High
250 kcmil126.7 mm²255 A5.68 V (2.37%)234.3 V9.38 V (3.91%)4184.5 WDrop/Amp High
300 kcmil152.0 mm²285 A4.74 V (1.97%)235.3 V7.82 V (3.26%)3488.0 WDrop/Amp High
350 kcmil177.3 mm²310 A4.06 V (1.69%)235.9 V6.7 V (2.79%)2990.3 WDrop/Amp High
400 kcmil202.7 mm²335 A3.55 V (1.48%)236.4 V5.86 V (2.44%)2615.6 WDrop/Amp High
500 kcmil253.4 mm²380 A2.84 V (1.18%)237.2 V4.69 V (1.95%)2092.2 WDrop/Amp High
600 kcmil304.0 mm²420 A2.37 V (0.99%)237.6 V3.91 V (1.63%)1744.0 WDrop/Amp High
750 kcmil380.0 mm²475 A1.9 V (0.79%)238.1 V3.13 V (1.3%)1395.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.42 V (0.59%)238.6 V2.34 V (0.98%)1046.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 150 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 150 feet one-way at 240V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.9V (0.79%) and delivers 238.1V at the load.

What size aluminum wire is required for 425 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.34V (0.98%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.