🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 175 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.92%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.74V (1.14%)
Voltage at Load End237.8 VLoss: 2.21 V (1627.7 W)
Power & Breaker (125%)176.67 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A403.97 V (168.32%)0.0 V666.37 V (277.65%)297373.7 WDrop/Amp High
12 AWG3.31 mm²20 A253.86 V (105.77%)0.0 V418.74 V (174.48%)186869.3 WDrop/Amp High
10 AWG5.26 mm²30 A159.75 V (66.56%)80.3 V263.51 V (109.79%)117592.6 WDrop/Amp High
8 AWG8.37 mm²50 A100.39 V (41.83%)139.6 V165.6 V (69.0%)73899.3 WDrop/Amp High
6 AWG13.3 mm²65 A63.18 V (26.32%)176.8 V104.21 V (43.42%)46506.6 WDrop/Amp High
4 AWG21.15 mm²85 A39.73 V (16.55%)200.3 V65.53 V (27.31%)29245.3 WDrop/Amp High
3 AWG26.67 mm²100 A31.51 V (13.13%)208.5 V51.97 V (21.65%)23192.2 WDrop/Amp High
2 AWG33.62 mm²115 A24.99 V (10.41%)215.0 V41.23 V (17.18%)18397.9 WDrop/Amp High
1 AWG42.41 mm²130 A19.81 V (8.26%)220.2 V32.68 V (13.62%)14584.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A15.71 V (6.55%)224.3 V25.91 V (10.8%)11563.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.46 V (5.19%)227.5 V20.56 V (8.56%)9173.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.88 V (4.12%)230.1 V16.3 V (6.79%)7276.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.84 V (3.27%)232.2 V12.93 V (5.39%)5769.9 WDrop/Amp High
250 kcmil126.7 mm²255 A6.63 V (2.76%)233.4 V10.94 V (4.56%)4881.9 WDrop/Amp High
300 kcmil152.0 mm²285 A5.53 V (2.3%)234.5 V9.12 V (3.8%)4069.3 WDrop/Amp High
350 kcmil177.3 mm²310 A4.74 V (1.97%)235.3 V7.82 V (3.26%)3488.6 WDrop/Amp High
400 kcmil202.7 mm²335 A4.15 V (1.73%)235.9 V6.84 V (2.85%)3051.5 WDrop/Amp High
500 kcmil253.4 mm²380 A3.32 V (1.38%)236.7 V5.47 V (2.28%)2441.0 WDrop/Amp High
600 kcmil304.0 mm²420 A2.76 V (1.15%)237.2 V4.56 V (1.9%)2034.7 WDrop/Amp High
750 kcmil380.0 mm²475 A2.21 V (0.92%)237.8 V3.65 V (1.52%)1627.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.66 V (0.69%)238.3 V2.74 V (1.14%)1220.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 175 feet one-way at 240V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 2.21V (0.92%) and delivers 237.8V at the load.

What size aluminum wire is required for 425 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.74V (1.14%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.