⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 50 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.26%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.78V (0.33%)
Voltage at Load End239.4 VLoss: 0.63 V (465.1 W)
Power & Breaker (125%)176.67 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 50 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A115.42 V (48.09%)124.6 V190.39 V (79.33%)84963.9 WDrop/Amp High
12 AWG3.31 mm²20 A72.53 V (30.22%)167.5 V119.64 V (49.85%)53391.2 WDrop/Amp High
10 AWG5.26 mm²30 A45.64 V (19.02%)194.4 V75.29 V (31.37%)33597.9 WDrop/Amp High
8 AWG8.37 mm²50 A28.68 V (11.95%)211.3 V47.31 V (19.71%)21114.1 WDrop/Amp High
6 AWG13.3 mm²65 A18.05 V (7.52%)221.9 V29.78 V (12.41%)13287.6 WDrop/Amp High
4 AWG21.15 mm²85 A11.35 V (4.73%)228.6 V18.72 V (7.8%)8355.8 WDrop/Amp High
3 AWG26.67 mm²100 A9.0 V (3.75%)231.0 V14.85 V (6.19%)6626.4 WDrop/Amp High
2 AWG33.62 mm²115 A7.14 V (2.98%)232.9 V11.78 V (4.91%)5256.5 WDrop/Amp High
1 AWG42.41 mm²130 A5.66 V (2.36%)234.3 V9.34 V (3.89%)4167.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.49 V (1.87%)235.5 V7.4 V (3.08%)3303.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.56 V (1.48%)236.4 V5.87 V (2.45%)2620.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.82 V (1.18%)237.2 V4.66 V (1.94%)2078.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.24 V (0.93%)237.8 V3.69 V (1.54%)1648.6 WDrop/Amp High
250 kcmil126.7 mm²255 A1.89 V (0.79%)238.1 V3.13 V (1.3%)1394.8 WDrop/Amp High
300 kcmil152.0 mm²285 A1.58 V (0.66%)238.4 V2.61 V (1.09%)1162.7 WDrop/Amp High
350 kcmil177.3 mm²310 A1.35 V (0.56%)238.6 V2.23 V (0.93%)996.8 WDrop/Amp High
400 kcmil202.7 mm²335 A1.18 V (0.49%)238.8 V1.95 V (0.81%)871.9 WDrop/Amp High
500 kcmil253.4 mm²380 A0.95 V (0.39%)239.1 V1.56 V (0.65%)697.4 WDrop/Amp High
600 kcmil304.0 mm²420 A0.79 V (0.33%)239.2 V1.3 V (0.54%)581.3 WDrop/Amp High
750 kcmil380.0 mm²475 A0.63 V (0.26%)239.4 V1.04 V (0.43%)465.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.47 V (0.2%)239.5 V0.78 V (0.33%)348.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 50 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 50 feet one-way at 240V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.63V (0.26%) and delivers 239.4V at the load.

What size aluminum wire is required for 425 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.78V (0.33%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.